Section 1 - General Specifications & Hazards

QUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST

6

DHI-300 FRONT

Section 14 - Troubleshooting

Visit our website at: www.lanair.com

47

DIMENSIONS:

DHI-300

Height: 61”

Width: 43”

Depth: 47”

Weight: 370 LBS

FIRING CAPACITIES:

DHI-300

Nozzle @ 1.86 gallons/hour, No. 2 fuel oil

Symptom

Possible Cause

Corrective Action

A. Burner will not start

1. Main electrical power

1. Reset breaker

circuit breaker tripped

2. Service disconnect

2. Turn switch on or

switch off or fuse blown

replace fuse

3. Thermostat turned down/

3. Turn thermostat up,

improperly installed/

check wires/test

defective

components/replace

4. Oil primary safety

4. Reset/test components,

tripped/defective

replace if needed

5. Too much light showing

5. Eliminate light to cad cell

on cad cell/defective

Test component

B. Burner attempts to fire,

1. Low oil in supply tank or

1. Fill tank, or drain and

but does not establish a

contaminated fuel

clean tank

flame

2. Plugged or worn nozzle

2. Clean or replace

3. Fuel pressure gauge

3. See section 6, Page 17

fluctuating/pumping system

4. Pre-heater switch is turned off

4. Turn switch on or test

or defective, or defective

switch and cartridge heater

cartridge heater

5. Transformer/electrodes not

5. Test transformer/look

sparking

for shorts & repair
Replace electrodes/
transformer

6. No air pressure/defective

6. Turn compressor on/test

regulator/defective solenoid

regulator/solenoid. Replace
defective components

7. Water in air system

7. Clean air pre-heater and

drain water from system

8. Combustion blower not

8. See flame adjustment

properly adjusted or

pages 29-31.

defective

Replace blower

9. Improper draft

9. Check draft see page 15.

Make sure chimney is
properly installed

10. Plugged heat exchanger,

10. Clean heater including

or chimney

manifold, chimney