Section 14 - Troubleshooting

QUESTIONS?... Contact Customer Service at 1-800-753-1601 M-F 8:00 am- 4:15 pm CST

46

Burner fuel pressure gauge reading hints:

Fuel gauge fluctuates (jumps):

• Suction Line Leak.
• Air in fuel, refer to Troubleshooting Chart Item B.
• Quad ring seal for the nozzle may be damaged.
• Seal in adapter block may be worn or damaged.
• Fuel pressure regulator seal leaking or dirty.
• Suction line strainer plugged or dirty.
• Dirty Pump Screen

Reading gradually decreases:

• Fuel pump output decreasing.
• Fuel viscosity decreasing.
• Orifice in nozzle is wearing.
• Dirty Pump Screen

Reading gradually increases:

• Fuel pump output increasing.
• Fuel viscosity increasing (cold fuel, and/or gear lube).
• Orifice in nozzle is becoming plugged.

Reading drops to –0- PSI when the burner is off.

• Dirt between the diaphragm and the seat in the by-pass regulator.
• Dirt between the plunger and the nozzle seat.
• Leak in the plumbing connections.
• Leak in the pre-heater assembly (damaged or missing o ring).
• Fuel pre-heater switch is off.

Steps to check the air operated fuel valve:

Disconnect the two transformer wires from the terminal block in the burner.

• Jump the cad cell circuit (refer to page 43).
• Disconnect the fuel supply pump orange wire from the terminal block inside the

burner.

• Set the dial indicator as shown on the diaphragm piston.
• Zero the dial indicator.
• Start the burner so that the air valve opens.

NOTE: The dial indicator should read +.015 to .050, which references the diaphragm piston
travel.

FRONT

REAR

LEFT SIDE

RIGHT SIDE

8" exhaust

View port

Fan Hi-Limit
switch

Clean Out

Access Panel

Blower Moter

Assembly

Electrical Access
Panel

Power Box

Burner
Assembly