5operating instructions, Tank-to-tank transfer, High pressure – Robinair 25200B Refrigerant Recovery Unit User Manual

Page 7: Warning

Advertising
background image

552701 Rev. A April 7, 2009

5

operating Instructions

Tank-To-Tank Transfer

When recovering refrigerant from one refillable tank into another, the color of the

hoses used for SYSTEM LIQUID and SYSTEM VAPOR may not match the color

of the liquid and vapor valves on the tank you are pulling the refrigerant from.

Confirm the hose for SYSTEM LIQUID is connected to the liquid valve of the tank,

and the hose for SYSTEM VAPOR is connected to the vapor valve of the tank.
1. Connect the hoses in the following manner.

Standard End connects to:

Ball Valve End connects to:

TANK LIQUID fitting on unit

LIQUID port on tank refrigerant

is being transferred into

TANK VAPOR fitting on unit

VAPOR port on tank refrigerant

is being transferred into

SYSTEM VAPOR fitting on unit

VAPOR port on tank refrigerant

is being transferred from

SYSTEM LIQUID fitting on unit

LIQUID port on tank refrigerant

is being transferred from

2. Follow Steps 1 through 5 in the Recovery Procedure on the previous page.

NOTE: Remember to monitor tank weight.

hIGh PressUre

If, during the recovery or self-clearing process, the HIGH PRESSURE light comes

on, verify all appropriate valves are open. If the valves are open and the light is

still on, there is an excessive amount of air or the tank is full. Follow these steps:
1. Press the COMPRESSOR switch to OFF.
2. Close both valves on the refillable tank, and close both valves on the red and

blue hoses connected to the tank.

3. Disconnect the red hose and the blue hose from the refillable tank.
4. Replace this tank with an empty refillable tank.
5. Reconnect the hoses as described in the Setup Instructions. Then follow the

steps in either the Recovery Procedure or the Self-Clearing Procedure.

If, after completing the above steps, either light is still on, call the Technical

Support Line at (800) 822-5561.

WarnInG

The refrigerant level in the tank must not exceed 80% of the tank

volume. Failure to monitor the level could result in excessive

hydrostatic pressures, causing physical injury or death.

Advertising