6operating instructions, Self-clearing procedure, Warning – Robinair 25200B Refrigerant Recovery Unit User Manual

Page 8

Advertising
background image

6

operating Instructions

self-ClearInG ProCedUre

CAUTION! Do not mix refrigerant types. Always perform the self-

clearing procedure after each recovery. Beginning each job with a

“clean” unit will help eliminate mixing of different refrigerant types.

1. Close the ball valves on the red and blue hoses connected to the A/C-R

system. Disconnect these hoses from the system’s access ports.

2. Close the blue LIQUID valve on the tank and the ball valve on the blue

TANK LIQUID hose. Disconnect the TANK LIQUID hose from the tank.

3. Verify the red TANK VAPOR hose is still connected to the red VAPOR fitting

on the tank. Both the tank’s red VAPOR valve and the ball valve on the red

TANK VAPOR hose should be open.

4. Press the switch to SELF-CLEAR. You will hear the compressor start and the

switch will illuminate.

5. Let the compressor run until the system pressure gauge reaches the

appropriate vacuum level. The system pressure gauge will return to

VACUUM. Press the COMPRESSOR switch to OFF. Unplug the unit from

the electrical source.

6. Close the red VAPOR valve on the tank and the ball valve on the red TANK

VAPOR hose. Disconnect the TANK VAPOR hose from the tank.

WarnInG

To prevent personal injury, disconnect hoses using extreme

caution. All hoses may contain refrigerant under pressure.

7. While the hoses are still connected to the unit, slowly open the ball valve

on each hose to relieve any pressure in the hose. Close the ball valves, then

disconnect the hoses from the unit.