D. residential garage installation, E. exhaust vent and intake pipe – HTP PHE199-119 User Manual

Page 11

Advertising
background image

11

LP-314 REV. 3.24.14

The space must be provided with combustion/ventilation air openings correctly sized for all other appliances located in the same space
as the appliance. Failure to comply with the above warnings could result in substantial property damage, severe personal injury, or
death.

D. RESIDENTIAL GARAGE INSTALLATION

PRECAUTIONS
If the appliance is located in a residential garage, per ANSI Z223.1:

Mount the bottom of the appliance

a minimum of 18” above the floor of the garage, to ensure the burner and ignition devices

are well off the floor.

When raising the appliance, be certain to fully support its entire filled weight.

Locate or protect the appliance so it cannot be damaged by a moving vehicle.

E. EXHAUST VENT AND INTAKE PIPE

The appliance is rated ANSI Z21.10.3 Category IV (pressurized vent, likely to form condensate in the vent) and requires a special vent
system designed for pressurized venting.

NOTE: The venting options described here (and further detailed in Venting, Part 8 in this manual) are the lone venting options
approved for this appliance. Failure to vent the appliance in accordance with the provided venting instructions will void the
warranty.

Failure to vent the appliance properly will result in serious personal injury or death.

Vents must be properly supported. Appliance exhaust and intake connections are not designed to carry heavy weight. Vent support
brackets must be within 1’ of the appliance and the balance at 4’ intervals. Appliance must be readily accessible for visual inspection for
the first 3’ from the appliance.

1. DIRECT VENT INSTALLATION OF EXHAUST VENT AND INTAKE PIPE
If installing a direct vent option, combustion air must be drawn from the outdoors directly into the appliance intake, and exhaust must
terminate outside. There are three basic direct vent options detailed in this manual: 1. Side Wall Venting, 2. Roof Venting, and 3.
Unbalanced Venting.

Be sure to locate the appliance such that the exhaust vent and intake piping can be routed through the building and properly
terminated. Different vent terminals can be used to simplify and eliminate multiple penetrations in the building structure (see Optional
Equipment in Venting Section). The exhaust vent and intake piping lengths, routing and termination methods must all comply with the
methods and limits given in the Venting section, Part 8 of this manual.

When installing a combustion air intake from outdoors, care must be taken to utilize uncontaminated combustion air. NOTE: To
prevent combustion air contamination, see Table 1.

2. INDOOR COMBUSTION AIR INSTALLATION IN CONFINED OR UNCONFINED SPACE
This appliance requires fresh, uncontaminated air for safe operation and must be installed in a mechanical room where there is
adequate combustion and ventilating air. NOTE: To prevent combustion air contamination, see Table 1.

Combustion air from the indoor space can be used if the space has adequate area or when air is provided through a duct or louver to
supply sufficient combustion air based on the appliance input. Never obstruct the supply of combustion air to the appliance. If the
appliance is installed in areas where indoor air is contaminated (see Table 1) it is imperative that the appliance be installed as direct
vent so that all combustion air is taken directly from the outdoors into the appliance intake connection.

Unconfined space is space with volume greater than 50 cubic feet per 1,000 Btu/hour (4.8 cubic meters per kW) of the total input
rating of all fuel-burning appliances installed in that space. Rooms connected directly to this space, through openings not furnished with
doors, are considered part of the space. See Figure 22, p. 41 for details.

Confined space is space with volume less than 50 cubic feet per 1,000 Btu/hour (4.8 cubic meters per kW) of the total input rating of
all fuel-burning appliances installed in that space. Rooms connected directly to this space, through openings not furnished with doors,
are considered part of the space.

When drawing combustion air from inside a conventionally constructed building to a confined space, such space should be provided
with

two permanent openings: one located 6” (15 cm) below the space ceiling, the other 6” (15cm) above the space floor. Each opening

Advertising
This manual is related to the following products: