HTP PHE199-119 User Manual

Page 52

Advertising
background image

52

LP-314 REV. 3.24.14

Figure 29

10. Press and hold ENTER for 4 seconds until you see the screen to log in the access code.

11. Use the  and  arrow keys to move the blinking zero to the left and right. Next,
use the

▲ and ▼ arrow keys on to log in the access code of 925. Press ENTER to

access the System Setting Program Navigation menu. Once the code is confirmed,
you can set the System Settings. Use  and  to navigate through the System Setting Program.

12. Press  3 times to scroll to Function 4 -

“WARM WEATHER OFF”. This is the warm weather shutdown. This function determines

the outdoor temperature that will turn off the hydronic heating module and operate the appliance only as an appliance for the warmer
weather. To adjust this value, press ENTER and the factory default of 68°F starts to blink. Use

▲ and ▼ to adjust this value to your

system needs. To store the new value press ENTER.

13. Next, press  once to scroll to Function 5 -

“MIN OUTDOOR TEMP”. This function is the first step to setting the outdoor reset

curve. Enter

your system’s minimum outdoor temperature value. To adjust the value, press ENTER and the factory default of 5 °F starts

to blink. Use

▲ and ▼ to adjust to your designed temperature. To store the new value press ENTER.


14. Press  once to scroll to Function 6 -

“MAX SUPPLY TEMP”. This function is the second step to setting your outdoor reset curve.

Enter

your system’s hydronic heating module maximum supply temperature value. To adjust the value, press ENTER and the factory

default of 140 °F will start to blink. Use

▲ and ▼ to adjust to your designed temperature. To store the new value press ENTER. NOTE:

This should be the same value entered in step 5.