11) pause input disable (parameter no.15) – IAI America ERC3 User Manual

Page 322

Advertising
background image

Chapter 6

Adjustment of Operation

6.3 I/O Parameter

6.3.1 Positioner Mode 1, Positioner Mode 2 and Pulse

Train Control Mode

312

(8) Default positioning width (in-position width) (Parameter No.10)

No.

Name

Symbol

Unit

Input Range

Default factory setting

10 Default positioning width

INP

mm

0.01

(Note 1)

to 999.99

0.10

When a target position is set in an unregistered position table, the setting in this parameter is

automatically written in the applicable position number. When the remaining moving distance

enters into this width, the positioning complete signal PEND/INP is output.

It is convenient to set the positioning width often used.

Note 1 It is down to the minimum positioning width (L = Lead length/800).

(9) Current-limiting value at standstill during positioning (Parameter No.12)

No.

Name

Symbol

Unit

Input Range

Default factory setting

12

Current-limiting value at

standstill during positioning

SPOW

%

1 to 70

35

By increasing the number, the retaining torque at a stop increases.

It is not necessary to change this setting in normal use, however, it is possible to block the

movement caused by external force by increasing the setting number when large external force

is applied at a stop. However, there is a risk that motor or controller may burn if the setting is too

high. Contact us if a change is required.

(10) Current-limiting value during home return (Parameter No.13)

No.

Name

Symbol

Unit

Input Range

Default factory setting

13

Current-limiting value during

home return

ODPW

%

1 to 100

In accordance with

actuator

The factory setting conforms to the standard specification of the actuator.

Increasing this setting will increase the home return torque.

It is not necessary to change this setting in normal use, however, home-return operation may

complete in front of the proper point in some cases depending on how it is installed or load is

attached when the product is vertically mounted. It is necessary to increase the setting value in

such cases. Other causes can also be considered, so contact us in advance to making a

change.

(11) Pause input disable (Parameter No.15)

No.

Name

Symbol

Unit

Input Range

Default factory setting

15 Pause input disable

FPIO

0 : Enabled

1 : Disabled

0

This parameter defines whether the pause input signal is disabled or enabled.

Set to “1” if pause by PIO is not to be performed.

Pause by PIO Signal cannot be performed if the setting is disable.

Also, operation becomes available with no pause signal input being connected.

Set Value

Description

0

Enable (Use the input signal)

1

Disable (Does not use the input signal)