IAI America ERC3 User Manual

Page 368

Advertising
background image

Chapter 7

Troubleshooting

7.2 Fault Diagnosis

358

7.2.2 Positioning and speed of poor precision (incorrect operation)

Situation

Possible cause

Check/Treatment

Completion of operation

on the way to home

return

In the home return of our standard

specification, the actuator is first pressed

to the mechanical end, moved oppositely,

and subject to positioning stop at the

home position. Therefore, the product

may judge as the mechanical end even

though it is still on the way when the load

is large and interfere with surrounding

object.

1) A load exceeding its rating weight is

installed on the actuator.

2) It is touched to interference in the way

of the run.

3) Torsion stress is applied to guide due

to improper fixing method of the

actuator or uneven fastening of bolts.

4) The sliding resistance of the actuator

itself is large.

1) Reduce the load.

2) Remove the interference.

3) Loosen the fixing bolts once and

check whether the slider can move

smoothly.

If the slider can move smoothly,

check if there is a deformation on

the attached surface, and install the

actuator again following the

instructions stated in Instruction

Manual.

4) Please contact IAI.

Shocks at start and/or

stop.

Acceleration/deceleration is set too high. Decrease the settings of

acceleration/deceleration.

Overshoot during

deceleration to stop.

The load inertia is large.

Decrease the setting of deceleration.

Positioning of poor

precision

Uneven speed during

movement

Acceleration/deceleratio

n not smooth (bad speed

response)

Trace of poor precision

[Refer to 6.3.1 [3] and 6.3.2 [3] Servo Adjustment.]

(Note) When the pulse-train operation mode is selected, first adjust pulse-train

commands.

[In the case of Positioner Mode]

Situation

Possible cause

Check/Treatment

Positioning at a position

different from that of

commanded position No.

PIO signal processing is incorrect.

1) Start signal CSTR is input too early

after position No. command. Or

position No. command and start signal

are input concurrently.

2) The correct position No. is not

specified due to PIO signal

disconnection or poor connector

contact.

1) The stop position may be set for

another purpose. Make sure to

complete the reading of the

position numbers to ERC3 before

inputting the start signal.

[Refer to Chapter 4, 4.2 Operation

in Positioner Mode and 10.6

Example of Basic Positioning

Sequence.]

2) Check the input signal on I/O

monitor on the teaching tool.

Complete signal PEND

is not output even

though positioning

process is completed.

PIO signal processing is incorrect.

1) Start signal CSTR is not turned OFF.

1) Make the start signal CSTR turned

OFF before completing the

positioning process by the turn-off

of positioning complete signal

PEND after starting operation, and

so on.