IAI America E-Con User Manual

Page 54

Advertising
background image

46

3. XSEL-R/S/RX/SX/RXD/SXD

(3) Example for when using DeviceNet and I/O Board 1 together

It is how to establish the setting when using DeviceNet to 192 points of each input and output from the top
of the extended I/O ports and assigning the I/O board (48 points for each input and output) to the standard
I/O ports.

Standard Input Ports No.0 to 191
Standard Output Ports No.300 to 491
(DeviceNet board)

Standard Input Port No.192 to 239
Standard Output Port No.492 to 539
(I/O board)

• I/O Parameters

No.

Parameter name

Default

(Reference)

Input Range

Unit

Remarks

1

I/O Port Allocation Type

1

0 to 1

0

0:Fixed Allocation
1:Automatic Allocation
•Reference 1 Priority of I/O Port Assignment

when automatically assigned

Port Number

(No.0 to 299/No.300 to 599)

1) Network I/F Module 1
2) I/O slot 1 (I/O1) Mounting board
3) I/O slot 2 (I/O2) Mounting board
* I/O slot 1 (I/O1) Assigned for the

continuously mounted range from
mounting board

•Reference 2 Priority of extension I/O ports at

automatic assignment

Port Number

(No.1000 to 3999/No.4000 to 6999)

1) Network I/F Module 2
2) Expansion I/O unit
3) IA Net

2

Standard I/O Fix-Allocated
Input Port Start No.

0

-1 to 599

192

0+ (Multiples of 8)
[Ineffective when -1 is selected]

3

Standard I/O Fix-Allocated
Output Port Start No.

300

-1 to 599

492

300+ (Multiples of 8)
[Ineffective when -1 is selected]