2.2 Explanation of Modes

2.2.1 Positioning

Mode

Push = 0

The actuator moves to the target position set in the “Position” field of the position table.










2.2.2

Push & Hold Mode

Push = Other than 0

(1) Load was contacted successfully

Upon reaching the target position set in the “Position” field of the position table, the actuator moves at the push
speed for the distance set in the “Positioning band” field.
If the actuator contacts the load while moving and the controller recognizes that “push action has completed,” the
position complete signal will turn ON.













 The push speed is set by parameter No. 34.

The factory setting varies with each actuator in accordance with the actuator’s characteristics.
Set an appropriate speed by considering the material and shape of the load, among others.
Since the maximum speed is 20 mm/s, operate the actuator at a speed not exceeding this value.

 Set a positioning band slightly longer than the last position, in order to absorb possible mechanical variation

of the load.

 “Completion of push action” is determined based on a combination of the current-limiting value set in the

“Push” field of the position table and the push completion judgment time set by parameter No. 6.
Set an appropriate condition by considering the material and shape of the load, among others.
For details, refer to Appendix 3, “Parameter Settings.”

Warning

 If the actuator contacts the load before reaching the target position, an overload or deviation

overflow alarm will generate. Pay due attention to the relationship of the target position and the
load position.

 The actuator continues to push the load at the push force at standstill determined by the

current-limiting value. Since the actuator is not inactive, exercise due caution when handling
the machine in this condition.

Speed

Moving distance

Positioning band

Time

Target position

The position complete
signal turns ON here.

Speed

Moving distance

Target position

Positioning band
(maximum push distance)

The position complete signal turns ON here,
as completion of push action is recognized
after the load has been contacted.