Communication signal details, 1 overview of communication signal timings, Overview of communication signal timings – IAI America RCM-GW-DV User Manual

Page 86

Advertising
background image

80

DeviceNet Gateway

7. Communication Signal Details

7.1

Overview of Communication Signal Timings


When a given control signal is turned ON to operate the ROBO Cylinder controller using the sequence
program in the PLC, the maximum response time before a response (status) signal will be received is
expressed by the formula below:

Maximum response time (msec) = Yt + Xt + 2 x Mt + Command processing time (operation time, etc.)

Mt = 10 (msec) x (n+1): SIO link (Modbus) cycle time
n: Number of controlled axes
Yt: Master

→ remote I/O station transmission delay

Xt: Remote I/O

→ master station transmission delay


For the master

→ remote I/O station transmission delay (Yt) and remote I/O → master station

transmission delay (Xt), refer to the operation manuals for your DeviceNet master unit and PLC.





























If a communication error occurs due to a problem along the transmission path, etc., a communication retry
or retries (up to three times) may occur, in which case the SIO link cycle time (Mt) will be extended.

DeviceNet
transmission delay

PLC sequence program

Control signal

Status signal

Master

→ remote I/O station

transmission delay (Yt)

Remote I/O

→ master station

transmission delay (Xt)

Gateway

Control signal

Status signal

Controller

Control signal

Status signal

SIO link cycle time

SIO link cycle time

Command

processing time