Inhibit terminals

Short the INHIBIT terminals to coast the motor to zero speed (see

Figure 10 for INHIBIT terminal location). Reopen the INHIBIT

terminals to accelerate the motor to set speed.

Twist inhibit wires and separate them from other power-carrying

wires or sources of electrical noise. Use shielded cable if the

inhibit wires are longer than 18 inches (46 cm). If shielded cable is

used, ground only one end of the shield to earth ground. Do not

ground both ends of the shield. See Shielding Guidelines, page 6.