Programming, Confi gure the kpr2000 – LiftMaster KPR2000 Single Entry Access Control Keypad and Proximity Reader User Manual

Page 5

Advertising
background image

5

PROGRAMMING

Programming Step

Keystroke Combination

1. Enter Program Mode

(Master Code) #

2. Pulse Mode
OR
2. Latch Mode

4 (1-99) # The relay time is 1-99 seconds
(default is 5 seconds)
4 0 # Sets the relay to ON/OFF latch mode

3. Exit Program Mode

4

Confi gure the KPR2000.

Change the configure settings according to your application (optional). Multiple configuration settings can be changed at one time: enter
program mode, change desired settings, then exit program mode.

SET MASTER CODE

The 6 digit Master Code is used to prevent unauthorized access to the
system. To interface with the KPR2000, the manager will need a Master
Code (factory default code: 888888). We highly recommend immediate
update and recording of your Master Code.

Programming Step

Keystroke Combination

1. Enter Program Mode

(Master Code) #

2. Update Master Code

0 (New Code) # (New Code) #

3. Exit Program Mode

SET ACCESS CONFIGURATION

There are 3 types of access configurations for the KPR2000:

• Card or PIN (Default): The User must present a valid Wiegand Card to

the KPR2000 or enter their PIN code followed by the # key, in order to
be granted access.

Card

Only: The User must present a valid Wiegand Card to the

KPR2000 in order to be granted access. The facility code and the ID
number are both read and validated as one block of Wiegand data.

• Card + PIN: The User must first present a valid Wiegand Card to the

KPR2000 and then enter their PIN code followed by the # key, in order
to be granted access.

Programming Step

Keystroke Combination

1. Enter Program Mode

(Master Code) #

2. Card Only
OR
2. Card + PIN
OR
2. Card or PIN

3 0 #

3 1 #

3 2 #

3. Exit Program Mode

SET RELAY CONFIGURATION

The relay configuration sets the behavior of the output relay on activation.

Programming Step

Keystroke Combination

1. Enter Program Mode

(Master Code) #

2. DOTL Alarm OFF

OR

2. DOTL Alarm ON

OR

2. DOTL Output Timing

6 0 #

6 1 # (Alarm sounds for 1 minute)

9 (1-3) #

3. Exit Program Mode

SET DOOR OPEN TOO LONG (DOTL) ALARM

This setting requires an external sensor input. The alarm output timing
can be set from 1-3 minutes (default is 1 minute). Factory default is OFF.

SET STRIKE-OUT ALARM

The strike-out alarm will engage after 10 failed card/PIN attempts. Factory
default is OFF. The strike-out alarm can be set to deny access for 10
minutes after engaging or it can be set to disengage only after entering a
valid master code or card.

Programming Step

Keystroke Combination

1. Enter Program Mode

(Master Code) #

2. Strike-Out OFF

OR

2. Strike-Out ON

OR

2. Strike-Out ON

7 0 # (Factory default)

7 1 # Access will be denied for 10 minutes

7 2 # Enter Master Code or Valid Card to
silence

3. Exit Program Mode

SET WIEGAND INPUT/OUTPUT OPTIONS

The KPR2000 offers input and output for industry standard Wiegand
devices (refer to Specifications). Default is HID 26 bit.

Programming Step

Keystroke Combination

1. Enter Program Mode

(Master Code) #

2. Set Wiegand Format

9 (Bit Format) # Bit Format = Valid 2 digit
format (example: 26 or 30)

3. Exit Program Mode

SET AUDIBLE AND VISUAL RESPONSE

Factory default is ON.

Programming Step

Keystroke Combination

1. Enter Program Mode

(Master Code) #

2. Control Backlight

OR

2. Control LED

OR

2. Control Sounds

ON = 7 5 #

ON = 7 7 #

ON = 7 9 #

OFF = 7 4 #

OFF = 7 6 #

OFF = 7 8 #

3. Exit Program Mode