System Sensor BEAM1224, BEAM1224S User Manual

System Sensor Equipment

Advertising
background image

INSTALLATION AND MAINTENANCE INSTRUCTIONS

BEAM1224, BEAM1224S
Single-ended Reflected Type
Projected Beam Smoke Detector

3825 Ohio Avenue, St. Charles, Illinois 60174

800/736-7672, FAX: 630/377-6495

www.systemsensor.com

D400-73-00

1 I56-2294-006R

SPECIfICATIONS
GENERAL
Range:

16 to 230 Feet (5 to 70m); 230 to 328 Feet (70 to 100m) using optional accessory BEAMLRK

Sensitivity:

25% to 50% Total Obscuration in 6 levels

Level 1 = 25%

Level 2 = 30%

Level 3 = 40%

Level 4 = 50%

Level 5 = 30% to 50% (Acclimate)

Level 6 = 40% to 50% (Acclimate)

Spacing:

30 to 60 Feet (9.1 to 18.3m)

Response Time:

ALARM - 20 seconds typical; TROUBLE - 30 seconds typical

Trouble Conditions:

Beam Blockage (96% or More Obscuration)

Improper Initial Alignment

Self-compensation limit reached (service needed)

In Alignment mode

Test/Reset Features:

Integral Sensitivity Test Filter (BEAM1224S only)

Sensitivity Filter (Incremental scale on reflector)

Local Alarm Test Switch

Local Alarm Reset Switch

Remote Test and Reset Switch Capability

Indicators:

ALARM - Remote Output, Local LED (red)

TROUBLE - Remote Output, Local LED (yellow), Blink Pattern Indicates Trouble Diagnostics

NORMAL OPERATION - Local LED (flashing green once every 5 sec.)

ALIGNMENT AIDS - Optical Gunsight (coarse adjustment), 00 to 99 Digital Display (fine adjustment)

RELAYS - Alarm; Trouble

SENSITIVITY - Digital Display Readout in Percent Obscuration

ENVIRONMENTAL
Temperature:

–22°F to 131°F (–30°C to 55°C); NOTE: For applications below 32°F (0°C), see Special Applications on page 2

Humidity:

10% to 93% RH Non-condensing

MECHANICAL
Shipping Weight:

Complete unit: 3.9 lbs. (1.77 kg)

Shipping Size:

15˝Ч10.5˝Ч6.5˝ (381mm × 267mm × 165mm)

Mounting:

Wall only without optional accessories

Wiring:

Plug-in Terminal Blocks (12 to 22AWG)

Adjustment Angle:

±10° Horizontal and Vertical

Paintable Trim Ring:

May be painted using enamel or acrylic type paints

ELECTRICAL
Voltage:

10.2 to 32 VDC (BEAM1224); 15 to 32 VDC (BEAM1224S)

Maximum Ripple Voltage:

6.0 volts (Peak-to-peak); NOTE: ripple must not fall below minimum operating voltage specification

Current (24 VDC):

Avg. Standby -

17mA Max.

Avg. Alarm -

38.5mA Max.

Avg. Trouble -

8.5mA Max.

Avg. Alignment -

28mA Max.

Current (Test Mode, BEAM1224S only):

Peak Test-

500mA Max.

Relay Contacts:

0.5A at 30 VDC

Reset Time:

0.3 Seconds Max.

Start-up Time (after 2 min. reset):

60 sec. Max.

Alarm Verification Time:

5 sec. Max.

Remote Output (Alarm & Trouble):

VOLTAGE - 15 to 32 VDC; NOTE: Output voltage same as device input voltage

CURRENT - 15mA maximum; 6mA minimum; NOTE: Output current is limited by 2.2Kohm resistor

I56-2294-006R

BEfORE INSTALLINg
Please thoroughly read this manual and applicable sections of System Sensor’s
Projected Beam Detector Application Guide. Copies of this manual are avail-
able from System Sensor.
gENERAL DESCRIPTION
System Sensor Model BEAM1224/BEAM1224S is a long range projected beam
smoke detector designed to provide open area protection. It is to be used

with UL-listed, separately supplied power (4-wire) control panels only. The
detector consists of a transmitter/receiver unit and a reflector. Smoke entering
the area between the transmitter/receiver and reflector causes a reduction in
signal. When the obscuration reaches alarm thresholds (chosen at the trans-
mitter/receiver unit), the detector generates an alarm signal. Complete block-
age of the beam causes a trouble signal. Slow changes in obscuration due to
a build up of dirt or dust on the lens of the detector are compensated for by