System Sensor BEAM1224, BEAM1224S User Manual

Page 9

Advertising
background image

D400-73-00

9 I56-2294-006R

APPENDIx I. OPERATION MODES AND TROUBLEShOOTINg gUIDE:

Modes

Red

Yellow

Green

Dual Digital

Display Readout Initiating Means

Alarm Contacts

Fault

Contacts

Comments &

Troubleshooting Tips

Alarm Remote

Normal

OFF

OFF

Blink

OFF

Successful

completion of

initialization or

detector reset

Open

OFF

Close

Alignment

OFF

ON

OFF

On, Relative amount

of signal 0-99, or

– if automatic gain

resetting, or Lo if

signal is too low

Alignment Switch

Open

OFF

Open

Alarm

ON

OFF

OFF

OFF

Smoke, Test Filter,

RTS451/KEY or

RTS151/KEY

Close

ON

Close

Trouble-Drift Comp

Elevated Signal

OFF

3 Quick

Blinks

Blink

OFF

Long Term Drift

Reference Out of

Range

Open

OFF

Open

• Sunlight into detector or reflector.

• Re-Align detector.

Trouble-Drift Comp

Reduced Signal

OFF

2 Quick

Blinks

Blink

OFF

Long Term Drift

Reference Out of

Range

Open

OFF

Open

Clean detector and reflector.

Trouble-Signal

Over Range

OFF

2 Quick

Blinks

Blink

OFF

Increase of

Reflected Signal

Open

OFF

Open

Inspect line of sight between

detector and reflector for reflective

objects in the pathway.

Trouble-Beam

Blockage Response OFF

4 Quick

Blinks

OFF

OFF

Beam Blockage

Open

OFF

Open

• Remove blockage.

• Faulty unit.

Initialization-

Power On

OFF Blink until

complete

Blink

OFF

Apply Power from

discharged state.

Open

OFF

Close

Initialization-

Alignment Exit

OFF Blink until

complete

Blink

OFF

Depressing

RESET switch after

alignment

Open

OFF

Close

Local Test

(BEAM1224S)

Pass Result

ON

Blinking the

amount of

drift used.

OFF

OFF

RTS451/KEY or

RTS151/KEY

Close

ON

Close

Detector remains in alarm until reset

or time-out

Local Test

(BEAM1224S)

Fail Result

OFF

On until

reset or

time-out

Blink

OFF

RTS451/KEY or

RTS151/KEY

Open

OFF

Open

Detector remains in fault until reset

or time-out

Local Test

(BEAM1224)

Fail Result

OFF

Per fault

mode

Blink

OFF

RTS451/KEY or

RTS151/KEY

Open

OFF

Open

If local test fails will already

be in fault

Local Test

(BEAM1224)

Pass Result

ON

Blinking the

amount of

drift used.

OFF

OFF

RTS451/KEY or

RTS151/KEY

Close

ON

Close

Blinks output by Yellow LED and Remote Trouble Output

once the device has passed a local remote test:

Percent The Detector Has Drifted

Number Of Blinks Output

<10%

None

<20%

1

<30%

2

<40%

3

<50%

4

<60%

5

<70%

6

<80%

7

<90%

8

<100%

9

Advertising