System Sensor BEAM1224, BEAM1224S User Manual

Page 7

Advertising
background image

D400-73-00

7 I56-2294-006R

fIgURE 12. COARSE ALIgNMENT PROCEDURE:

EYE

REFLECTOR

C0265-00

fIgURE 13. OUTER hOUSINg SCREw LOCATIONS:

SCREW LOCATIONS

RESET SWITCH

C0266-00

STEP 3. SENSITIvITy SELECTION
Set the sensitivity of the detector using the sensitivity switch (Figure 10) and
digital display. Use the chart below to determine which setting is acceptable
(per UL 268) for your installed distance. Before attempting to set the sensi-
tivity, make sure that you have completed the fine adjustment process (the
digital display should be “OFF”). To set the sensitivity, depress the sensitivity
button once. The digital display will illuminate and read the current sensi-
tivity setting as indicated on the chart. Continue to depress the sensitivity
button until the desired setting is achieved. The display will turn off auto-
matically. The default sensitivity will be factory set at level 4 or 50%.

In addition to the four standard sensitivity selections the detector has two Ac-
climate settings. When either of these settings is chosen the detector will au-
tomatically adjust its sensitivity using advanced software algorithms to select
the optimum sensitivity for the environment. The sensitivity will be continu-
ously adjusted within the ranges specified in the chart above.

Sensitivity

Setting

Percent

Obscuration

Display

Reading

Acceptable Distance

Between Detector & Reflector

Feet

Meters

Level 1

25

25

16.4 to 120

5.0 to 36.6

Level 2

30

30

25 to 150

7.6 to 45.7

Level 3

40

40

60 to 220

18.3 to 67

Level 4

50

50

80 to 328

24.4 to 100

Acclimate

Level 1

30 to 50

A1

80 to 150

24.4 to 45.7

Acclimate

Level 2

40 to 50

A2

80 to 220

24.4 to 67

Total obscuration can be converted to percent per foot, assuming uniform
smoke density for the entire length of the beam. The chart below converts
total obscuration to percent per foot for all acceptable sensitivity settings.

2.0

1.5

1.0

0.5

0.0

0

25% SETTING

30% SETTING

40% SETTING

50% SETTING

50

100

150

200

250

300

350

OBSCURA

TION (%/FT

.)

SENSITIVITY IN PERCENT PER FOOT VS. DISTANCE

(ASSUMES UNIFORM SMOKE DISTRIBUTION)

DISTANCE IN FEET

C0268-00

STEP 4. COMPLETINg ThE INSTALLATION
Refer to Figure 13 for this step.

1. Tighten the optics lock down screws so the optics are secure. Take spe-

cial care not to shift or disturb the optics. Use a hand screwdriver to
avoid over-tightening or jarring the optics.

2. Install the outer housing of the detector, making sure to tighten all four

screws in each corner of the housing.

NOTE: The housing contains a gasket seal that protects the detector from
moisture.
3. Remove the protective film from the front surface of the outer housing.
4. Press the reset button, making sure to avoid blocking the line-of-sight

between the detector and reflector. The yellow LED will begin to blink
for about 20 seconds. At this time, the detector is making its final gain
adjustment to compensate for the effects of installing the outer housing.
When the gain adjustment is complete, the yellow LED will turn off and
the green LED will begin blinking, indicating a successful gain adjustment.

5. Install the trim ring by snapping it onto the outer housing. If the trim ring

was painted, ensure that the paint is completely dry before installing.

STEP 5. fINAL vERIfICATION
1. Block the entire reflector with an opaque material. Nearly any non-re-

flective opaque material will do, including this manual or the cardboard
packaging inserts. The detector should enter a trouble condition, indi-
cated by the fault relay and the yellow LED (see Appendix 1) after 30
seconds. If the detector does not enter a trouble condition, there is a
problem with the installation. Refer to troubleshooting section in Appen-
dix 1 for assistance.

2. Complete a sensitivity test of the detector. Refer to the Sensitivity Testing

section of this manual for the appropriate procedure.

3. Remove the orange adhesive-backed sheet used to aid in coarse adjustment.
Congratulations. You have completed the final installation and alignment pro-
cedure.
SENSITIvITy TESTINg
NOTE: Before testing, notify the proper authorities that the smoke detector
system is undergoing maintenance, and therefore the system will be tempo-
rarily out of service. Disable the zone or system undergoing maintenance to
prevent unwanted alarms.

Detectors must be tested after installation and following periodic maintenance.
The sensitivity of the BEAM1224/BEAM1224S may be tested as follows:

NOTE: Before testing the detector, check for the presence of the flashing green
LED at the receiver, making sure not to disturb or block the beam. If it does
not flash and the detector is not in trouble or alarm, power has been lost to
the detector (check the wiring).
A. Calibrated Test Filter
The sensitivity of the detector can be tested using an opaque material to cover
the reflector by an amount indicated by the graduated scale on the reflector.
(Due to the high optical efficiency of the reflector the selection of the opaque
material used to block the reflector is not critical. Acceptable materials in-
clude, but aren’t limited to, this manual or the cardboard packaging inserts.)

Refer to Figure 14 for this procedure.

1. Verify the sensitivity setting of the detector in % obscuration. See the

Sensitivity Selection section of this manual for sensitivity determination
if sensitivity is unknown.