System Sensor 5600 Series Heat Detectors User Manual

System Sensor Equipment

Advertising
background image

Before Installing
This detector must be installed in compliance with

the control panel installation manual and meet the

requirements of NFPA 72, and/or the local authority

having jurisdiction.
Read this manual carefully before using the detec-

tor. This manual should be left with the owner/user

of this equipment.
General Description
The 5600 series mechanical heat detector is in-

tended for use in property protection applications,

or for non-life-safety installations where smoke de-

tection is not practical or appropriate.

WARNING

For life-safety installations, smoke detectors must

be used, in lieu of, or in addition to mechanical heat

detectors.

The 5600 series consists of both single- and dual-

circuit heat detectors featuring fixed temperature

thermal sensors or combination fixed temperature/

rate-of-rise sensors, with temperature ratings of 135ºF

(57ºC) or 194ºF (90ºC).

D500-46-00

1

I56-2175-003R

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

5600 Series
Mechanical Heat Detector
Single Circuit: 5601P, 5602, 5603, 5604
Dual Circuit: 5621, 5622, 5623, 5624

Markings on the exterior of the detector indicate the

specific activation method and temperature rating. All

models are identified as either 135ºF/57ºC or 194ºF/

90ºC. Models equipped with combination fixed tem-

perature/rate-of-rise sensors are marked FX/ROR.

Fixed temperature only models are marked FX.
Non-Resettable Fixed Temperature Sensor
The fixed temperature element reacts to heat by re-

sponding to a specific temperature setting (135ºF

or 194ºF). The detection method is based on the

spring action of a metal contact, held to the metal

chamber by a fusible alloy. When the temperature

reaches the alloy’s melting point, the metal contact

will depress the diaphragm, causing the electrical

contact to close the circuit. The circular external

heat collector is released from the detector to visu-

ally indicate that the detector has been activated.
NOTE: 5600 series Fixed Temperature models (5603,

5604, 5623, and 5624) are non-resettable, and can-

not be tested.

Specifications:

Operating Voltage/Contact Ratings (Resistive): 6 – 125 VAC / 3A

6 – 28 VDC / 1A

125 VDC / 0.3A

250 VDC / 0.1A

Maximum Installation Temperature:

Models 5601P, 5603, 5621, and 5623: 100°F (38°C)

Models 5602, 5604, 5622, and 5624: 150°F (65.6°C)

Alarm Temperature:

Models 5601P, 5603, 5621, and 5623: 135°F (57°C)

Models 5602, 5604, 5622, and 5624: 194°F (90°C)

Rate-of-Rise Threshold:

15°F (8.3°C) per minute

(models 5601P, 5602, 5621, and 5622 only)

Operating Humidity Range:

5 to 95% RH non-condensing

Input Terminals:

14 – 22 AWG

Back Box Mounting:

3

1

2

˝ octagonal

4˝ octagonal

Single gang

4˝ square with a square to round plaster ring

Dimensions with mounting bracket:

Diameter: 4.57 inches (11.6cm)

Height: 1.69 inches (4.3cm)

Weight:

6 oz. (170 grams)

CAUTION

To prevent the activation of the fixed temperature element, the shipping and storage temperature must not

exceed 122°F (50°C).

I56-2

175-00