System Sensor 5600 Series Heat Detectors User Manual

Page 2

Advertising
background image

Self-Restoring Rate-of-Rise (ROR) Sensor
The rate-of-rise element responds to a rapid rise of

temperature, approximately 15ºF (8.3ºC) per min-

ute. As the temperature rises, the air within the

sealed chamber expands. Should the chamber air

expand faster than it can escape through the cali-

brated vent, the diaphragm is depressed, and the

electrical contact closes the circuit.
NOTE: Only the ROR element of 5600 series com-

bination fixed temperature/ROR models (5601P,

5602, 5621, and 5622) are self-restoring, and may be

tested using a hair dryer or heat gun. When testing

the ROR element, to prevent the activation of the

fixed temperature element, the heat source must not

exceed the fixed temperature rating of the detector.

Mounting Bracket
All 5600 series detectors are equipped with a mount-

ing bracket that includes mounting slots to accom-

modate single-gang, 3

1

2

˝ octagonal, and 4˝ octagonal

electrical boxes, as well as 4˝ square boxes equipped

with a plaster ring (Figure 1). The mounting bracket

is reversible to accommodate flush-mount and sur-

face–mount installations (Figure 2).

Wiring Installation Guidelines

All wiring must be installed in compliance with the

National Electrical Code, applicable state and local

codes, and any special requirements of the local

Authority Having Jurisdiction. Proper wire gauges

should be used. The conductors used to connect

heat detectors to the alarm control panel and ac-

cessory devices should be color-coded to reduce the

D500-46-00

2

I56-2175-003R

Heat Detector Type

RTI Classification

Fixed 135°F RTI:

SPECIAL

RoR and Fixed 135°F RTI:

ULTRA FAST and SPECIAL (Respectively)

Fixed 194°F RTI:

SPECIAL

RoR and Fixed 194°F RTI:

ULTRA FAST and SPECIAL (Respectively)

FM Classification
RTI ratings are for installations which must comply with FM 3210.

Table 1. 5600 Series Mechanical Heat Detectors

Model

No.

Circuit

Temperature

Rating

Thermal Sensor

UL Maximum Spacing

(10-foot ceiling)

5601P

Single

135ºF (57ºC)

Fixed Temperature/Rate of Rise

50-feet x 50-feet

5602

Single

194ºF (90ºC)

Fixed Temperature/Rate of Rise

50-feet x 50-feet

5603

Single

135ºF (57ºC)

Fixed Temperature

25-feet x 25-feet

5604

Single

194ºF (90ºC)

Fixed Temperature

25-feet x 25-feet

5621

Dual

135ºF (57ºC)

Fixed Temperature/Rate of Rise

50-feet x 50-feet

5622

Dual

194ºF (90ºC)

Fixed Temperature/Rate of Rise

50-feet x 50-feet

5623

Dual

135ºF (57ºC)

Fixed Temperature

25-feet x 25-feet

5624

Dual

194ºF (90ºC)

Fixed Temperature

25-feet x 25-feet

NOTE: Refer to NFPA72 guidelines for spacing reductions when ceiling heights exceed 10 feet.

A= 3

1

2

˝ Octagonal box

B= 4˝ Octagonal box
C= Single gang box and 4˝
square with plaster ring
D= Directly to Wall/Ceiling

Figure 1. Bracket Mounting Locations: