System Sensor 5600 Series Heat Detectors User Manual

Page 3

Advertising
background image

D500-46-00

3

I56-2175-003R

likelihood of wiring errors. Improper connections

can prevent a system from responding properly in

the event of a fire.
The non-polarized screw terminals on the back of

the detector will accept 14–22 AWG wire. For best

system performance, all wiring should be installed

in separate grounded conduit; do not mix fire alarm

system wiring in the same conduit as any other

electrical wiring. Twisted pair may be used to pro-

vide additional protection against extraneous elec-

trical interference.
Wire connections are made by stripping approxi-

mately

1

4

˝ of the insulation from the end of the feed

wire, inserting it into the proper base terminal, and

tightening the screw to secure the wire in place.

+

EOL

OR

Control

Panel

Auxiliary

Device

Auxiliary

Device

Auxiliary

Device

Auxiliary

Device

Auxiliary

Device

Control

Panel

+

OR

EOL

Figure 3. Wiring Diagram – Single Circuit Models:

Figure 4. Wiring Diagram – Dual Circuit Models:

Installation
Remove power from the alarm control unit or initi-

ating device circuits before installing detectors.
1. Detach the detector from the mounting bracket by

rotating the detector 1⁄4 turn counter-clockwise.

2. Orient the mounting bracket properly for either a

flush- or surface-mount installation (Figure 2).

3. Select the pair of mounting holes suitable for the

junction box, (Figure 1) and secure the bracket

to the box.

4. Connect the wires to the detector per Figure 3 or

Figure 4, as applicable.

5. Place the detector onto the mounting bracket by

rotating clockwise. The detector will lock into

place with a “click”.

6. After all detectors have been installed, apply

power to the alarm control unit.

7. Test each detector as described in Testing.

8. Reset all the detectors at the alarm control unit.

9. Notify the proper authorities that the system is

in operation.