Installation instructions nbox(b)tmne, g, h, 4 installation - configuration, Exit configuration – TREND NBOX(B)TMNE, G, H User Manual

Page 11: Configure gsm modem settings, Set up device (communicating by way of tmn), Devices

Advertising
background image

NBOX(B)TMNE, G, H Trend Modem Node Controller Installation Instructions TG200729 Issue 2, 07/01/2009

11

Installation Instructions

NBOX(B)TMNE, G, H

• If 94x is using both TMNs/ANCs and XN28s then see Auto-dialling manual. If 94x is 945 1.01 or greater see

945 Engineering Manual.

• 962/963 can automatically seek next available autodialler (ANC, MNC, TMN, XN28) or can have particular

devices allocated to particular autodiallers (e.g. to ensure XN28s are used correctly).

• If dialling a TMNG, use its data number
• In 963, using TMNG, in Tcommsrv.ini set IdleTimeToDropline=100, and RemoteATDSites=60000 and ensure

[Grouping] has ‘TMN-G=G’.

• In PowerTool using TMNG in TrendCommsCodes.ini change mG=German Modem to ‘mG=TMN’, and add

‘cG=GSMIntegral’.

1

4

2

3

6

5

7

*

8

9

#

0

PHONE

94x/

962/963

modem

963

mobile phone

allows 963 to transmit
text messages (SMS)
to mobile phone, (no
need for TMN)

direct

SMS

modem

(

963 SMS

)

direct

Exit Configuration

23

X

 " Exit from Utility"

1.4 Installation - Configuration

(continued)

Configure GSM modem settings

22

TMNG only

As a result of inserting the SIM card (1.4 step 10), select ‘init’ from top level config prompts
(see 1.4 step 18) to automatically re-initialize modem (v4.5 and greater only).
For TMNG v4.4 the settings must be entered manually:
• In configuration mode with the top menu prompts displayed, type 'direct'.
• Type “dAT+CNMI=2,1,1,0,0” to enable SMS received notification
• Type “dAT+CSMS=1” to set SMS commands to Phase 2+ version
• Type “dAT+ILRR=0” to disable data rate reports
• Type “dAT+CAOC=1” to disable charging information reports
• Type “dAT+CMGF=1” to set SMS message mode to text
• Type “dAT+CSMP=17,196,0,0” to set SMS validity period to 4 weeks
• Type “dAT+CSAS” to save the SMS settings
• Type “dAT&W” to save settings to modem stored profile

RS232

Set up device (communicating by way of TMN)

24

Devices:

TMN

TMN

Lan

I/N

IQ/822

WupDn

IQ/822

TMN

Device

TMN

• For autodialled or critical alarms target, set Outstation address as appropriate with Lan number set to zero if

TMN a local Lan, and set to destination Lan number if TMN on Internetwork. Put outstation address, Lan, and
phone number in TMN record.

• IC Comms - use with caution - see Auto-dialling manual

• WupDn doesn't inform if connected

• If dialling a TMNG, use its data number

direct

only old IQ or 822+/Toolbox -
see 1.4 steps 9 and 17

TMN

TMN

Lan

I/N

921

921

modem

direct

using SANC - no need for TMN.

• Use 921 auto-dialling mode. Use '==' method to put Lan number in auto-dial number table, and enter TMN address

- see 921 Manual.

• If dialling a TMNG, use its data number

TMN

TMN

Lan

I/N

921/

SET

921/

SET*

modem

direct

using SANC - no need for TMN.

• Use 921 auto-dialling mode. Either set autodialler address to 2 to find any available TMN (Lan or I/N), or set

autodialler address to specific TMN address.

• If 921 shares TMNs/ANCs and XN28s then they must be specifically addressed.
• If dialling a TMNG, use its data number

TMN

TMN

Lan

I/N

94x/

962/963

921 < v 2.5

IQ
822+/Toolbox

WupDn

RS232

RS232

921 => v 2.5
SET

94x Series/962/963

(+841, 842, 843, 845)

*SET v4

PowerTool

Advertising