Roll follower adjust input (optional), Remote mode selector switch (optional) – Warner Electric TCS-200-1H User Manual

Page 9

Advertising
background image

9

Warner Electric • 800-825-9050

P-2003-2 • 819-0420

o 5. Connect the red wire from the high resistance

end of the remote potentiometer to terminal 7 of
terminal block TB1 of the TCS-200-1. Secure the
terminal screw.

o 6. Connect the shield lead from the cable to

terminal 11 of terminal block TB1 of the
TCS-200-1. Secure the terminal screw.

Roll Follower Adjust Input (Optional)

Refer to Figure 4b for roll follower adjust input
connections.

o 1. Wire a three conductor shielded cable to the

roll follower potentiometer previously installed.

Note: Using a shielded cable with wire colors red,
black, and green is recommended to simplify
potentiometer and terminal connections:

a. Black wire to low resistance end terminal of
potentiometer.
b. Red wire to high resistance end terminal of
potentiometer.
c. Green wire to wiper terminal of potentiometer.

o 2. Route the cable from the sensor potentiometer

to the control, keeping the cable segregated from
high voltage AC Power lines and other wiring that
may cause noise transients.

o 3. Connect the black wire from the low

resistance end of the roll follower potentiometer
to terminal 11 of terminal block TB1 of the
TCS-200-1. Do not tighten the terminal screw.
Snug down only.

o 4. Connect the green wire from the wiper of the

roll follower potentiometer to terminal 9 of
terminal block TB1 of the TCS-200-1. Secure the
terminal screw.

o 5. Connect the red wire from the high resistance

end of the roll follower potentiometer to terminal
8 of terminal block TB1 of the TCS200-1. Secure
the terminal screw.

o 6. Connect the shield lead from the cable to

terminal 11 of terminal block TB1 on the
TCS-200-1. Secure the terminal screw.

Remote Mode Selector Switch (Optional)

Refer to Figure 5a for the remote mode selector
switch connections.

o 1. Install selector switch at a convenient location.

o 2. Wire a three conductor shielded cable to the

external mode selector switch.

Note: It is recommended that a shielded cable with
wire colors of red, black, and green be used as this
will simplify switch and terminal connections.

a. Black wire to common contacts of both switch
poles.
b. Red wire to normally open contact for "on" or
"stop" pole.
c. Green wire to normally open contact for "off"
pole.

PI:1000Ω, 1/2 WATT,

10% TOLERANCE,

0.5% LINEARITY,

LINEAR TAPER

TB1

1 2 3 4 5 6 7 8 9 10 11

PI

REMOT

E

POT

W

IP

ER

COMMON

CW

PI:1000Ω, 1/2 WATT,

10% TOLERANCE,

0.5% LINEARITY,

LINEAR TAPER

TB1

1 2 3 4 5 6 7 8 9 10 11

PI

ROL

L

FOLLOWER

W

IP

ER

COMMON

CW

Remote torque adjust input

Figure 4a

Roll follower adjust input

Figure 4b