INDOOR HEATER

The design is also certified for indoor installation when equipped with the approved draft hood.
For Canada, indoor installation is restricted to an enclosure that is not occupied and does not directly

communicate with occupied area. Refer to the latest edition of CAN/CGA-B149.1 and B149.2 for specific
requirements.

Locate heater as close as practical to a chimney or gas vent. Heater must always be vented to the outside. See

Vent Piping Section for venting details. Minimum allowable space is shown on the nameplate.

Fig. #8246.5

12

6. Attach the three (3) mounting brackets to the

stack using the screws provided and the holes
that are pre-drilled in the stack. Make sure the
brackets are positioned with the flange near the
top side of the stack (see illustration).
Caution must be taken not to over tighten and
strip the screw threads.

7. Turn the assembled stack and jacket top, right side

up. The jacket top will be trapped between the
brackets and the top of the stack. Place the stack
over the inner adapter panel flanged hole and lower
the louvered jacket top panel back into its original
position. Reinstall the four (4) green #10 flat head
screws removed in step 1 above.

VENT TERMINAL/INDOOR STACK INSTALLATION

WARNING:

Indoor boilers require a drafthood that must be connected to a vent pipe and properly vented to the outside. Failure

to follow this procedure can cause fire or fatal carbon monoxide poisioning.

1. Remove the louvered jacket top by removing

four (4) #10 flat head screws.

2. If originally installed, remove "Pagoda" top

from the louvered jacket top.

3. Place the inner stack adapter panel over the

flue collector inside the heater. Make sure
the flanged side of the flue opening is up.

4. Turn the stack (draft hood) up side

down and set it down bottom side up.

5. Turn the jacket top panel (removed in step 1) up

side down and place it through the stack.

DRAFTHOOD

JACKET TOP PANEL

(part of the heater)

#10 SHEET METAL SCREW (3)

MOUNTING BRACKET (3)

FLUE COLLECTOR

(part of heater)

SCREW HOLE
LOCATION

3-1/4"

INNER STACK ADAPTER PANEL