Series 27 Solenoid Piloted Valves with L-O-X

®

Control

Remote Control in a Full Range of Valve Sizes

PILOT DE-ENERGIZED

With the solenoid pilot de-energized

(regardless of the position of the

L-O-X

®

handle) the inlet poppet

remains closed. The outlet port is

connected to the exhaust port so that

pressure in the downstream lines is

vented to atmosphere.

PILOT ENERGIZED

With the solenoid pilot energized and

the L-O-X

®

control in the open posi-

tion, air can flow from inlet to outlet

port. The exhaust port is closed.

L-O-X

®

VALVE CLOSED

With the handle pushed inward, the

L-O-X

®

control is closed, and air to

the valve piston is cut off. This allows

the inlet poppet to be closed by its

spring and the pressure of the inlet

air. The outlet is connected to exhaust

so downstream pressure is vented.

Following any FRL components, an energy isolation valve is usually

the first valve in the line supplying compressed air to equipment. The

energy isolation valve should provide a quick means of shutting off the

supply of air and exhausting the downstream lines.

The shut-off function of the solenoid pilot controlled L-O-X

®

valve is the

same as that of the manual L-O-X

®

valves. A short, full inward push

of the red operating handle closes off the flow of air, and exhausts the

pressure in the downstream line. In addition, the solenoid pilot controlled

allows the air supply to be turned on or off by remote electrical control

whenever the L-O-X

®

handle is in the outward position. Air flows only if

the L-O-X

®

handle is outward and the solenoid pilot is energized. When

the L-O-X

®

handle is pushed in, air will not flow regardless of the pilot

being energized or not. As with all L-O-X

®

valves, the L-O-X

®

handle

can be padlocked in the closed position. As a further precaution against

inadvertent air flow, the solenoid pilot controlled has no manual override.

Because of the poppet construction of the main valve body, air pressure

provides the forces both to open the valve and to close it. These are

large forces so that quick response is ensured even after the valve has

been on standby for a long time.

VALVE OPERATION

The position of the red handle indicates instantaneous
full flow pressurizing or exhausting capability.

1

2

3

PILOT

VALVE

1

2

3

PILOT

VALVE

1

2

3

PILOT

VALVE

B

C

A

1

2

3

3

3

Y

Y

For coordinating silencers,

see page 18 (model numbers

5500A4003, 5500A6003,

5500A8001 and 5500A9002).

Port Size

Valve Model Avg. Cv

Dimensions inches (mm) Weight

In-Out Exh.

Number*

1 to 2 2 to 3

A

B

C

lb (kg)

1/4

1/2 Y2773A2072

2.5

3.1

7.1 (181)

8.4 (212)

6.5 (165)

3.5 (1.6)

3/8

1/2 Y2773A3072

3.6

5.3

7.1 (181)

8.4 (212)

6.5 (165)

3.5 (1.6)

1/2

1/2 Y2773A4082

3.3

5.3

7.1 (181)

8.4 (212)

6.5 (165)

3.5 (1.6)

1/2

1

Y2773A4072

6.3

9.2

7.1 (181)

9.0 (228)

6.9 (175)

4.3 (1.9)

3/4

1

Y2773A5072

7.7

11

7.1 (181)

9.0 (228)

6.9 (175)

4.3 (1.9)

1

1

Y2773A6082

8.0

12

7.1 (181)

9.0 (228)

6.9 (175)

4.3 (1.9)

1 11/2 Y2773A6072

23

34

8.1 (206)

11.8 (299) 6.9 (175)

8.0 (3.6)

11/4 11/2 Y2773A7072

30

32

8.1 (206)

11.8 (299) 6.9 (175)

8.0 (3.6)

11/2 11/2 Y2773A8082

30

31

8.1 (206)

11.8 (299) 6.9 (175)

8.0 (3.6)

11/2 21/2 Y2773A8072

68

70

9.3 (235)

13.8 (352) 7.3 (184)

17.5 (7.9)

2 21/2 Y2773A9072

70

70

9.3 (235)

13.8 (352) 7.3 (184)

17.5 (7.9)

21/2 21/2 Y2773A9082

70

71

9.3 (235)

13.8 (352) 7.3 (184)

17.5 (7.9)

STANDARD SPECIFICATIONS: For valves on this page.

Ambient Temperature: 40° to 120°F (4° to 50°C).

Media Temperature: 40° to 175°F (4° to 80°C).

Flow Media: Filtered air; 5 micron recommended.

Inlet Pressure: Port sizes 1/4 to 1

1/2: 15 to 150 psig (1.0 to 10.3 bar).

Port sizes 1

1/2 to 21/2: 30 to 150 psig (2.1 to 10.3 bar).

*Body Paint: Yellow.

*Port Threads: NPT standard. For BSPP threads, insert a “D” after

“Y” to the model number, e.g. YD2773A2072.
NOTE: Per specifications and regulations, these products are
defined as energy isolation devices, NOT AS EMERGENCY
STOP DEVICES.

L-O-X

®

Sensing Port

L-O-X

®

Sensing Port - Series 15 manual L-O-X

®

valves and manual L-O-X

®

valves with EEZ-ON

®

operation are now provided with 1/8

NPT sensing ports, enabling installation of a pressure sensing device such as the Pop-Up Indicator or Pressure Switch shown below.
Standards suggest that machine design should include a method for verifying the release of energy after lockout.

The ROSS 988A30 Pop-Up Indicator is constructed for the industrial environment with a brass body and 1/8” NPT connection. It offers
360° visibility and a redundant verification feature. By pushing on the red plunger, the operator can “feel” the presence of pressure
and verify that the indicator is performing its sensing function.
The ROSS 586A86 Pressure Switch offers an electronic pressure sensing option that can be integrated into a safety monitoring system,
which confirms energy isolation throughout the circuit.