Maple Systems STEPware-100 User Manual

Page 23

Advertising
background image

Network Grounding
To communicate properly, serious attention must be paid to the grounding scheme of the

devices connected to the com-link. Improper grounding, improper termination, and faulty

shielding of the com-link are the most common causes of system failure in a multidrop

network.
The cable shield must not be used as the signal ground.

It is tempting to try and reduce the cost of 5-wire cabling by using a 4-wire cable with the

shield used as the signal ground. DON’T DO IT. The initial cost savings are always

exceeded by the maintenance costs once the system is operating under field conditions. It

is often necessary to completely replace the network com-link with the proper cable

(5-wire plus shield) to eliminate noise problems in the system.

The signal ground must not be connected to the chassis or earth ground.

The chassis or earth ground is intended as a safety ground for power supplies, EMI

filters, voltage spike protection circuits, 120 VAC neutral returns, and all manner of AC

and DC driven devices. As a result, the chassis or earth ground can carry large voltage

potentials and currents. Connecting the signal ground to chassis or earth ground can

damage the devices connected to the com-link.

20

STEP1 Protocol Operation Manual

1010-0096, Rev. 04

HOST TERMINATION

470 Ohm

to

10 KOhm

Tx+

Tx-

Vcc

Rx+

Rx-

SIGNAL GND

CHASSIS GND

EARTH

GROUND

TERMINA

TO

R

HOST

OIT3600

120 Ohm

to

240 Ohm

FROM HOST +

FROM HOST -

TO HOST +

TO HOST -

SIGNAL GND

SHIELD

DO NOT

CONNECT

END TERMINATION

470 Ohm

to

10 KOhm

120 Ohm

to

240 Ohm

MAP460D

OIT3160

TERMINA

TO

R

Shield

Signal Ground

From Host +

To Host +

Shield

To OIT

To OIT

Signal Ground

From Host

To Host

From Host -

To Host -