Delayed linefeed setting, Use 3-wire rs-485 setting – Maple Systems STEPware-100 User Manual

Page 33

Advertising
background image

To modify this parameter in Configuration mode:
1. At Turn Delay:, use the OIT’s TOGGLE key to select the desired turnaround delay.

Refer to the Configuration Mode section in this chapter for more information.

To modify this parameter from the host controller:
1. Use the Set Turn-Around Delay control command. Refer to Appendix A: Control

Commands for more information.

Delayed Linefeed Setting

This parameter determines whether the OIT executes an LF control code (hexadecimal

0A) immediately or when the next character is received. If enabled, the OIT does not

execute an LF control code received from the host controller until the next character is

received. If disabled, the OIT immediately executes the LF control code. This parameter

is used most often with host controllers that automatically append an LF control code to

each data transmission.
To modify this parameter using STEPware-100:
1. Open the Configuration Editor.
2. In the OIT Operational Settings group box, select the Delayed LineFeed Enabled check

box.

To modify this parameter in Configuration mode:
1. At Delayed LF:, use the OIT’s TOGGLE key to enable or disable delayed linefeed.

Refer to the Configuration Mode section in this chapter for more information.

To modify this parameter from the host controller:
1. Use the Display and Cursor Format Control control command. Refer to Appendix A:

Control Commands for more information.

Use 3-Wire RS-485 Setting

This parameter determines whether the OIT disables the RS-485 receiver when the OIT

transmits data to the host controller. If the OIT is wired to the host controller using 3-wire

RS-485 half duplex communications, then this option must be enabled for the OIT to

operate properly. Conversely, if the OIT is wired to the host controller using 5-wire RS-485

full duplex communications, this setting must be disabled to allow the host controller to

send a command to the OIT while waiting for a response from a prior command.
To modify this parameter using STEPware-100:
1. Open the Configuration Editor.
2. In the OIT Operational Settings group box, select the Use 3-Wire RS-485 check box.
To modify this parameter in Configuration mode:
1. At RS485 3 Wire:, use the OIT’s TOGGLE key to enable or disable 3-Wire RS-485.

Refer to the Configuration Mode section in this chapter for more information.

30

STEP1 Protocol Operation Manual

1010-0096, Rev. 04