1. Control Panel Design Guidelines

Pay careful attention to the placement of system components and associated cable

routing. These items can significantly enhance the performance and integrity of

your control application.

1.1. Control Panel Grounding

• The control panel should be connected to a good, high-integrity earth ground

both for safety considerations and shielding purposes. This must be a reliable

earth ground with a low-resistance path. The ideal earth ground would be a

copper grounding rod located close to the OIT and the control panel.

• Hinged doors on control panels do not provide a long term electrical connection

to the rest of the enclosure. Corrosion develops over time and prevents good

electrical contact. For this reason, a separate wire braid should be installed from

the hinged control panel to the rest of the enclosure.

1.2. Power Supply Selection

• The power supply used to power the OIT should have an output between +12

and +30 VDC. The voltage should measure between +12 and +30V at the OIT

between Pins 2 and 3 of the OIT terminal block. A 24 VDC, 0.5 amp linear

power supply dedicated to the OIT is recommended.

• The power leads on the operating cable for the OIT should be 18AWG

2-conductor wire with a shield wire and protective shield foil. The shield of the

OIT operating cable must be connected to earth ground at both ends of the cable.

Please refer to Section 2.2.

6

MAP460D

1010-0093, REV 03

I / O CONTROL LINES

CONTROLLER

GROUND WIRES

OIT REAR

COVER

GROUND

STRAP

POWER LINE

FILTER

QUIET GROUND(ISOLATED)

QUIET

GROUND

LINE

FILTER

OIT

POWER

SUPPLY

OIT

SHIELDED

COMMUNICATION

CABLE

CONTROL PANEL

TIED TO RELIABLE

EARTH GROUND

CABLE

OIT OPERATING

Figure 1 Control Panel Example