Serial Mode Select Switch

Switch

No.

Description

ON

OFF

RS-232C RS-422 RS-485

1

Internal setting

Reserved

Reserved

OFF

*1

*1 Be sure to keep the settings OFF.

OFF

*1

OFF

*1

2

Changes COM1’s
communication
method

RS-422/RS-485

RS-232C

OFF

ON

ON

3

Changes COM1’s
communication
method

RS-422/RS-485

RS-232C

OFF

ON

ON

4

Changes SD (TXD)
data’s output mode

SD (TXD) data
output is
controlled via the
RS (RTS) signal.

SD (TXD) data
output is NOT
controlled via the
RS (RTS) signal.
(normally output)

OFF

ON/
OFF

ON/
OFF

*2

*2 Set switches number 9 and 10 to ON when the SD (TXD) output driver is automatically controlled

with RS (RTS). Set switch number 4 to OFF.
Set switches number 9 and 10 to OFF when the SD (TXD) output driver is controlled with the RS
(RTS) signal. Set switch number 4 to ON.

5

Switches the SD
(TXD) termination
resistance ON/OFF

Inserts
termination
resistance of
220

Ω between

SDA and SDB.

No termination

OFF

ON

ON/
OFF

*3

*3 If you use the termination resistance, base your settings on the connection specifications.

6

Switches the RD
(RXD) termination
resistance ON/OFF

Inserts
termination
resistance of
220

Ω between

RDA and RDB.

No termination

OFF

ON

ON/
OFF

*3

7

Switches the
shorting of SDA and
RDA ON or OFF

Shorts SDA and
RDA
(RS-485 mode)

No shorting
(RS-422 mode)

OFF

OFF

ON

8

Switches the
shorting of SDB and
RDB ON or OFF

Shorts SDB and
RDB
(RS-485 mode)

No shorting
(RS-422 mode)

OFF

OFF

ON

9

RS (RTS) Automatic
control mode
(enabled only when
RS-485 mode)

The data is
automatically
controlled via the
RS (RTS) signal.

The data is not
automatically
controlled via the
RS (RTS) signal.

OFF

OFF

ON/
OFF

*2

10

OFF

OFF

ON/
OFF

*2