Switched dc, 20ma process, Install and wire – Watlow Series 93 User Manual

Page 13: Figure 2.7a, Figure 2.7b

Advertising
background image

W a t l o w S e r i e s 9 3

I n s t a l l a n d W i r e

2 . 7

Figure 2.7a –

Switched DC

93_ _- 1 C _ _- 00 _ _

Figure 2.7b –

4-20mA Process

93_ _- 1 F_ _- 00 _ _

Maximum load impedance: 800

External

Load

10

9

-

+

10

unregulated

V+

V—

9

Internal Circuitry

7 to 10V (dc)

94

External

Load

10

9

-

+

Install and Wire

NOTE:

Successful installa-
tion requires four
steps:

• Choose the con-
troller’s hardware
configuration and
model number
(Appendix);

• Choose a sensor
(Chapter Two and
Appendix);

• Install and wire
the controller
(Chapter Two);

• Configure the

controller (Chapters
Three, Four and
Five).

NOTE:

When an external
device with a non-
isolated circuit com-
mon is connected to
the 4-20mA or dc
output, you must use
an isolated or un-
grounded thermo-
couple.