Output 2 Wiring

Figure 2.8a

– Mechanical Relay Without Contact Suppression

93_ _- 1 _ D _ - 00_ _

Form C, 5A

Minimum load current:
100mA @ 5VÎ (dc)

Figure 2.8b

– Solid-state Relay Without Contact Suppression

93_ _- 1_ K _- 00_ _

0.5A (ac loads only)

Figure 2.8c –

Switched DC

93_ _- 1_ C _ - 00_ _

7

unregulated

V+

V—

6

Internal Circuitry

7 to 10V (dc)

94

External

Load

7

6

-

+

External

Load

7

1

Fuse

L1

L2

Customer-supplied

Quencharc for inductive

loads only. See note.

6 COM

NC 1

7 NO

L1

L2

External

Load

Fuse

Customer-supplied

Quencharc for inductive

loads only. See note below.

Install and Wire

2 . 8

I n s t a l l a n d W i r e

W a t l o w S e r i e s 9 3

NOTE:

Successful installation
requires four steps:

• Choose the controller’s
hardware configuration
and model number
(Appendix);

• Choose a sensor
(Chapter Two and
Appendix);

• Install and wire the
controller (Chapter Two);

• Configure the con-

troller (Chapters Three,
Four and Five).

NOTE:

Output is in open state in
Alarm Condition.

NOTE:

Switching inductive loads
(relay coils, solenoids,
etc.) with the mechanical
relay, switched dc or
solid-state relay output
options requires use of an
R.C. suppressor.

Watlow carries the R.C.
suppressor Quencharc
brand name, which is a
trademark of ITW Paktron.
Watlow Part No. 0804-
0147-0000.

ç

WARNING: To avoid dam-
age to property and equip-
ment, and/or injury or
loss of life, use National
Electric Code (NEC) stan-
dard wiring practices to
install and operate the
Series 93. Failure to do
so could result in such
damage, and/or injury or
death.