<7. Operation>

7-5

IM 01C27F01-01EN

NOTE

If the transmitter searches the Field Wireless

Network for long time at low ambient

temperature condition, sometimes error “AL.70

LOWBAT” is displayed on the Integral Indicator.

Even though using new batteries, it can occur. It

occurs because of battery characteristics. After

joining to the Field Wireless Network, this error

will be cleared within one hour if battery has no

failure.

7.5 Shutting Down the

Transmitter

Shut down the transmitter as follows.

1) Remove the battery pack or set the transmitter

to deep sleep mode by the device configuration

tool.

2) Close the stop valve.

3) Close the tap valves.

NOTE

• Whenever shutting down the transmitter for a

long period, remove the transmitter from the

process line.

• Refer to subsection 9.4.5 “Replacing the

Battery Pack” for the battery pack removing.

• When storing the instrument with a battery

pack inserted, it is recommended to put the

instrument into deep sleep mode to conserve

battery power. For details on how to switch to

deep sleep mode, refer to subsection 8.3.12

“Switching to the Deep Sleep Mode.”