<8. Setting Parameters>

8-18

IM 01C27F01-01EN

NOTE

When the device detects AL01 and AL02, the

LCD display stays on regardless of the status

in LCD mode. See Table 9.3 and 9.4 Alarm

Message for details.

8.3.4 Tag and Device Information

If these are specified when ordering, the designated

Tag No. and device information are set and

shipped. Tag No. and device information can be

checked as follows.

• Procedure to call up the tag No. and device

information
- Device Tag ( Software Tag )

This is specified when writing characters (up

to 16 characters) of amplifiers TAG that differ

from characters specified in Tag No.

Refer to section 7.4 “Connection to the Field

Wireless Network” for confirmation.

- Tag Description

This is a universal parameter to store the

comment that describes the content of the

tag located in the TRANSDUCER and AI

blocks.

The AI1 and AI3 blocks of the AI blocks

correspond to the pressure and temperature,

respectively.

• When changing the device information, input

the information based on the following limitation

on the number of characters.
- Message function (up to 32 characters)

TRANSDUCER block : Tag Description

AI1, AI3 block : Tag Description

8.3.5 Unit

The unit parameter is set at the factory before

shipment if specified at the time of order. Follow the

procedure below to change the unit parameter.

• Procedure to call up the Unit display (Units

Index)

Al1, Al3 block : Scale.Units Index

To change the Unit display, choose desired unit

among the list of displayed unit selecting AI1

block as for the pressure, and AI3 block as for

temperature in the AI blocks.

8.3.6 Range Change

The range values are factory-set as specified by

the customer. To change the range, follow the steps

below.
The measurement span is determined by the upper

and lower range values. In this method, the upper

and lower range values can be set independently,

and the span changes according to the range limit

values sent to the transmitter.

• Procedure to call up the PV Range display.

AI1 block : PV Range

Select the AI1 block for the pressure, then

select “EU at 0%” and “EU at 100%” displayed

in the PV Range parameters. And input the

lower range and upper range values for the

range.

8.3.7 Output Signal Low Cut Mode Setup

Low cut mode can be used to stabilize the output

signal near the zero point.

( There is 10% of hysteresis at only point of

transition from low to high)
[Setup Low Cut Value]

• Procedure to call up the Lower cutoff* display

AI1 block : Lower cutoff*
Example: setup LOW_CUT of output to 15%
Lower cutoff*

= (“Eu at 100%” - “Eu at 0%”) × 0.15 + “Eu at 0%”

*: “Low Cutoff” is used instead of “Lower cutoff” for

Detachable antenna type (Amplifier housing code: 8 or

9).

[Setup Low Cut Mode]

• Procedure to call up the Low Cut Mode display

AI1 block : Low Cut Mode

F0804.ai

(%)

50

20

0

50 (%)

For low cut in Linear mode

For low cut in Zero mode

Example:

Low cut 20%

Input

(%)

50

20

0

50 (%)

Example:

Low cut 20%

Input

Output

Output

Figure 8.3

Low Cut Mode