11 software write protect, Software write protect -21 – Yokogawa EJX530B User Manual

Page 54

Advertising
background image

<8. Setting Parameters>

8-21

IM 01C27F01-01EN

(2) Span Adjustment
Span Adjustment is function to change the input and

output characteristic that assumed the bottom value

(zero point) of measurement range a standard.
Therefore, perform span adjustment (adjustment

of the upper limit value) after zero adjustment

(adjustment of bottom limit value).
After adding the pressure at point of adjustment and

setting pressure value as parameter, the transmitter

calculates quantity of adjustment and performs

adjustment automatically.

• Procedure to call up the lower limit value

parameter (Calibration Lowest Point)

AI1 block: Calibration Lowest Point

Set the lower limit adjustment value on the

pressure (AI1 block) Calibration Lowest

Point parameter screen. Apply a reference

pressure corresponding to the lower limit of the

measurement range to the pressure transmitter

and confirm the pressure when it stabilized.

• Procedure to call up the calibration adjustment

parameter (Cal Cmd)

AI1 block: Cal Cmd: CAL_LOW

Confirm the lower limit of the measurement

range in CAL_LOW of the pressure (AI1 block)

Cal Cmd parameter.

• Procedure to call up the calibration status

parameter (Cal Status)

AI1 block: Cal Status

Confirm the calibration status of CAL_

SUCCESS (1) using the Cal Status parameter.

• Procedure to call up the upper limit adjustment

parameter (Calibration Highest Point).

AI1 block: Calibration Highest Point

Set the upper limit adjustment value for the

pressure (AI1 block) Calibration Highest

Point parameter. Apply a reference pressure

corresponding to the upper limit of the

measurement range to the pressure transmitter

and confirm the when it has stabilized.

• Procedure to call up the calibration adjustment

parameter (Cal Cmd).

AI1 block: Cal Cmd: CAL_HIGH

Confirm the upper limit of the measurement

range in CAL_HIGH of the pressure (AI1 block)

Cal Cmd parameter.

• Procedure to call up the calibration status

parameter (Cal Status)

AI1 block: Cal Status

Confirm the calibration status of Cal Status (1)

using the Cal Status parameter.

(3) Reset Adjustments
Reset Adjustment clear the amount of adjustment.

Reset Adjustment can be performed using

CAL_CLEAR of the pressure (AI1 block) Cal Cmd

parameter for the input pressure. After calibration,

confirm status by using the pressure (AI1 block) Cal

Status.
The amount of adjustment made by the external

zero-adjustment screw can be reset to the initial

setting as well.

• Procedure to call up the calibration adjustment

parameter (Cal Cmd).

AI1 block: Cal Cmd: CAL_CLEAR

8.3.11 Software Write Protect

Hardware write protection and software write

protection functions are available for this transmitter

• Procedure to call up the protection setting

parameter (UAP Option)

UAPMO block: UAP Option

The following settings can be configured in the

UAP Option parameter.
- Setting to enable or disable software write

protection.

- Setting to enable or disable the hardware

write protection switch.

- Setting to enable or disable changing

the setting to the Diagnostic Switch and

Diagnostic Configuration parameters.

• Procedure to call up the protection setting

display parameter (Hardware Write Protect)

UAPMO block: Hardware Write Protect

The Hardware Write Protect parameter enables

the switch status of hardware write protection to

be displayed.

For the relationship between hardware write

protection and software write protection, refer

section 10. “Parameter Summary”.