Yokogawa Removable Chassis DX1000N User Manual

Page 153

Advertising
background image

3-36

IM 04L41B01-17E

TAG_PRIORITY

Tag prioritized display

DISP_GROUP

Group number display

SEPARATOR

When p2 is set to LOG (select from the
items below)

LOGIN_LOG

Login log

ERROR_LOG

Error log

COMMU_LOG

Communication log

FTP_LOG

FTP log

WEB_LOG

Web log

MAIL_LOG

E-mail log

SNTP_LOG

SNTP log

DHCP_LOG

DHCP log

MODBUS_LOG

Modbus log

OPERATE_LOG

Operation log

SETTING_LOG

Change settings log

DISP_ITEM

Switches the

displayed

item

s

SEPARATOR

When p2 is set to 4PANEL (select from the
items below)

4PANEL1 to 4PANEL4 Selects 4-panel

SEPARATOR

When p2 is set to CUSTOM_PANEL (select
from the items below)

INTERNAL1 to INTERNAL3

Selects one from internal 1 to 3

EXTERNAL1 to EXTERNAL25

Selects one from external 1 to 25

NEW

New

When p2 is set to ANNUNCIATOR (select
from the items below)

EXPAND

Expand

SEPARATOR

Example Register the following items to the Trend main

menu’s sub menu: SCALE and DIGITAL.
SM DISP_SUB,TREND,SCALE,DIGITAL

Description • Items that you can set for p3 and subsequent

parameters vary depending on p2.

• If parameter p3 and subsequent parameters

are omitted, all menu items are hidden.

• A command error occurs if you specify the

same menu item multiple times.

• You can specify up to three separators. If you

specify more than three, an error occurs.

• You cannot specify EXPAND for log and

4-panel.

• You cannot omit parameters using delimiters

(, ,).

• The SM DISP_SUB? command causes the

DX to return sub menu items whose display is
turned off.

• You cannot set the first menu item to

“SEPARATOR.”

• The display group parameter “GROUP1” to

“GROUP36” and the auto switching parameter
“AUTO” on/off setting apply to the trend,

digital, bar graph, and historical trend menus.
(For example, if you set AUTO to off for the
trend menu, and then set AUTO to on for the
digital menu, AUTO is turned on for the trend,
digital, bar graph, and historical trend menus.)

• When p2 is set to ANNUNCIATOR, the

DX1000 does not have submenus.

• When p2 is set to INFORMATION, you can

only set p3 to DISP_GROUP on the DX1000.

• When p2 is set to OVERVIEW, you can only

set p3 to ALARMACK on models with the /AS1
advanced security option.

• When p2 is set to LOG, you can only set

p3 to OPERATE_LOG, SETTING_LOG,
or DISP_ITEM on models with the /AS1
advanced security option. LOGIN_LOG
cannot be specified on models with the /AS1
advanced security option.

Setting the function menu

p1 Type (FUNC)
p2 ≥ Menu items to display
The DX displays the functions that you select

from below in the menu in the specified order.

The DX does not display menu items that are

not specified.

ALARMACK

Alarm acknowledge

ALARM_RESET

Alarm display reset

MESSAGE
FREE_MESSAGE
MEDIA_EJECT
SNAPSHOT
MANUAL_SAMPLE
TRIGGER

Event trigger

SAVE_DISPLAY
SAVE_EVENT
SAVE_STOP
MATH_START/STOP
MATH_RESET
MATH_ACK

Computed data dropout
acknowledge

EDGE_SWITCH

Presses event edge
switch

TIMER_RESET
MATCH_T_RESET

Resets single match
time timer

KEYLOCK

Enables or disables key
lock

LOGOUT
PASSWORD_CHANGE
RATE_CHANGE

Display rate 1 or display
rate 2

BATCH
TEXT_FIELD
FAVORITE_REGIST

Registers as favorite

4PANEL
JUMP_DISPLAY

Registers the screen to
return to

3.4 Setting Commands