App index – Yokogawa Removable Chassis DX1000N User Manual

Page 235

Advertising
background image

6-9

IM 04L41B01-17E

Specifications

1

2

3

4

5

6

App

Index

Input Register Data

Data Type

306001

List of alarms of measurement channels 001 to 004

Bit string

|

|

306012

List of alarms of measurement channels 045 to 048

• Register structure

4ch 3ch 2ch 1ch

Level 3

Level 4

Level 2

Level 1

Indicates the alarm status of four channels in one register. Set to 1 when alarm is

activated.

The figure is an example of register 306001 (measurement channels 001 to 004).
306021

List of alarms of computation channels 101 to 104

Bit string

|

|

306035

List of alarms of computation channels 157 to 160

• Register structure: Same as the list of alarms of measurement channels.
306041

List of alarms of external input channels 201 to 204

Bit string

|

|

306100

List of alarms of external input channels 437 to 440

• Register structure: Same as the list of alarms of measurement channels.
* Input registers 306001 to 306100 can be accessed consecutively. All unassigned register bits

are read as zeroes.

Input Register Data

Data Type

309001

Year

16-bit signed integer

309002

Month

309003

Day

309004

Hour

309005

Minute

309006

Second

309007

Millisecond

309008

DST

6.3 Modbus Protocol Specifications

Advertising
This manual is related to the following products: