App index, Xt temperature unit settings, Sw daylight saving time settings – Yokogawa Standalone MW100 User Manual

Page 36: Ss daylight saving time operation settings, Ba settings of strain input initial balancing, Un unit number settings, Sv rolling average settings

Advertising
background image

1-29

IM MW100-17E

Commands

1

2

3

App

App

Index

XT

Temperature Unit Settings

Setting

XTp1<terminator>
p1 Units of temperature
DEG_C

Temperature calculated in °C

DEG_F

Temperature calculated in °F

Query

XT?

Example

Temperature units set in °F

XTDEG_F

Explanation When the temperature units are changed, the settings

of the SR, SF, XB, XJ, XD, AO, AP, and ST commands
are initialized.

SW

Daylight Saving Time Settings

Setting

SWp1,p2,p3,p4,p5<terminator>
p1 Starts/stops date/time type
START

Start date/time

END

Exit date/time

p2 Date/time-month
JAN

January

FEB

February

MAR

March

APR

April

MAY

May

JUN

June

JUL

July

AUG

August

SEP

September

OCT

October

NOV

November

DEC

December

p3 Date/time-week
1st

First week

2nd

Second week

3rd

Third week

4th

Fourth week

LAST

Final week

p4 Date/time-day of week
SUN

Sunday

MON

Monday

TUE

Tuesday

WED

Wednesday

THU

Thursday

FRI

Friday

SAT

Saturday

p5 Date/time-hour (0 to 23)

Query

SW[p1]?

Example

Star Daylight Saving time on April, first week, Sunday, 2
hours.
SWSTART,APR,1st,SUN,2

SS

Daylight Saving Time Operation

Settings

Setting

SSp1<terminator>
p1 Summer time operation valid/invalid

ON/OFF

Query

SS?

Example

Enables Daylight Saving time.
SSON

BA

Settings of Strain Input Initial

Balancing

Setting

BAp1,p2<terminator>
p1 Channel range (001 to 060)
p2 Initial balancing valid/invalid (ON/

OFF)

Query

BA[p1]?

Example

Enable strain input initial balance operation on channel
1.
BA001,ON

Explanation Specify measurement channels on p1.

UN

Unit Number Settings

Setting

UNp1<terminator>
p1 Unit number (00 to 89)

Query

UN?

Example

Set unit number to 5.
UN05

SV

Rolling Average Settings

Setting

When p2=OFF
SVp1,p2<terminator>
p1 MATH channel number (A001 to A060)
p2 Rolling average ON/OFF (OFF)
When p2=ON
SVp1,p2,p3,p4<terminator>
p1 MATH channel number (A001 to A060)
p2 Rolling average ON/OFF (ON)
p3 Sampling interval (1 to 6S, 10S, 12S,

15S, 20S, 30S, 1M to 6M, 10M, 12M,
15M, 20M, 30M, or 1H)

_S: Interval setting in unit of

seconds

_M: Interval setting in unit of

minutes

_H: Interval setting in unit of hours
p4 Number of samples (1 to 1500)

Query

SV[p1]?

Example

Set the sampling interval to 1 minute and the number of
samples to 360 on MATH channel A001.
SVA001,ON,1M,360

Explanation • This command can be used on models with the /M1

math option.

• Set the sampling interval to an integer multiple of the

MATH interval.

1.4 Setting Commands (System Related)

Advertising