Yokogawa DAQWORX User Manual

Page 21

Advertising
background image

2-10

IM WX1-07E

Decimal point:

Set the offsetting decimal place for writing to registers. Select 0, 1, 2, 3, 4,

or 5.

Span minimum/maximum :

Setting range:

–1E9 to 1E9

If the value requested by AddObserver is outside of the span range, it is

not output.

Units:

Specify using six alphanumeric characters or fewer.

Note

Registers 41280 (UTM, USM, UPM) and 41281 (SMP) of the UT520, UT550, UT551, UT750,

US1000, UP550, and UP750 cannot be written using the Modbus/RTU, Modbus/TCP protocol.

Please make note of this.

Input link:

Displays and selects the tag for intput that is linked to the output tag.

Displayed in the format xx:tag name where xx is the input tag name.

When you click an input select button, the tag selection dialog box is

displayed.

Input select button

Click here to display the Tag Selection dialog box.

Links are not set

Click here (blue) to apply the edited register numbers

in the input tag to the output tag

Display the tag that links are not set of registered tags

of the input tab page

Output value: Specifies an output value for the output test.

Range: –1E9 to 1E9

Loaded value:

The output register value is displayed after the output test.

If the output value is outside of the output span, “Out range” is

displayed. If a communication error occurs during output, “Com error”

is displayed.

2.2 Enterng Envronment Settngs