Troubleshooting guide – Sterling QVES User Manual

Page 27

Advertising
background image

27

7. Defective

thermocouple

(Standing pilot units only).

8. Drafts around unit.

9. Pilot valve not opening (faulty

wiring).

10. No spark (if applicable) (faulty

wiring).

11. Defective gas valve.
1. Loose

wiring.

2. Defective motor overload protector or

defective

motor.

3. Defective power venter relay.

1. Fan relay heater element improperly

wired.

2. Defective venter relay switch.
3. Motor overload protector cycling on

and

off.

4. Motor not properly oiled.
1. Improperly wired venter relay.
2. Main burners not lighting while

thermostat calls for heat.

3. Defective venter relay.
1. Incorrect gas input.
2. Heater

undersized.

3. Thermostat

malfunction.

4. Heater cycling on limit control.

5. Check outside dampers if used.

7. Check thermocouple connection,

and replace if defective.

8. Eliminate drafts. Refer to

"Installation".

9. Inspect and correct all wiring.

10. Inspect and correct ignition system

wiring. See symptoms W, X,& Y.

11. Replace.
1. Check and tighten all wiring connec-

tions per diagrams. Thermostat wires

tagged "W" and "G" must be

connected together (unless special

thermostats are used; if so, see

thermostat wiring diagram). See

electrical

connections.

2. Replace

motor.

3. Check for 24V across 1 and 3

terminals on fan relay. If 24V is

present, jumper terminals numbered

2 and 4. If motor runs, the relay

is defective and must be replaced.If

24V is not present, check wiring per

diagrams.

1. Be sure venter relay heater terminals

are connected per diagrams.

2. Replace venter relay.
3. Check motor amps against motor

name plate rating, check voltage,

replace power venter motor if defective.

4. Refer to label on motor.
1. Check all wiring.
2. Refer to H & N symptoms.

3. Replace venter relay.
1. Refer to "Operation".
2. This is especially true when the heated

space is enlarged. Have the heat loss

calculated and compare to the heater

output (80% of input). Your gas

supplier or installer can furnish this

information. If heater is undersized,

add additional heaters.

3. Replace

thermostat.

4. Check air movement through heat

exchanger. Check voltage to fan

motor. Clean power venter blade and

heat exchanger and oil power venter

motor.
5. Adjust dampers accordingly.

Troubleshooting Guide

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

N. Pilot will not light or will not
stay lit. continued

O. Power venter will not run.

P. Power venter motor turns on

and off while burner is

operating.

Q. Power Venter motor will not
stop.

R. Not enough heat.