Suspension, Figure 5 – Sterling QVES User Manual

Page 8

Advertising
background image

8

SUSPENSION

The duct furnace must be hung level from side to side and front to back, from four

suspension points provided at the top of the unit. Failure to do so will result in poor performance and/or
premature failure of the unit. Refer to Figure 5 for typical suspension arrangements. DO NOT mount duct
furnaces in series (one in front of another).

NOTICE: When mounting duct furnaces side by side, units must have opposite side gas connections
(determined by Digit #6 - Furnace Type in the unit number). Minimum safety clearances must also be
maintained; see Table 3. When service/accessibility clearances are greater than minimum safety clearances,
service/accessibility clearances take precedence. See “Accessibility” section under “Installation”.

MAKE CERTAIN THAT THE STRUCTURE TO WHICH THE

FURNACE IS TO BE MOUNTED IS CAPABLE OF SAFELY SUPPORTING ITS

WEIGHT. UNDER NO CIRCUMSTANCES MUST THE GAS LINES, VENTING

SYSTEM OR THE ELECTRICAL CONDUIT BE USED TO SUPPORT THE

HEATER OR ANY OTHER OBJECTS (I.E. LADDER, PERSON) LEAN

AGAINST THE HEATER GAS LINES, VENTING SYSTEM OR ELECTRICAL

CONDUIT FOR SUPPORT. FAILURE TO HEED THESE WARNINGS MAY

RESULT IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

MAKE CERTAIN THAT THE LIFTING

METHODS USED TO LIFT THE UNIT HEATER ARE

CAPABLE OF SUPPORTING THE WEIGHT OF THE

HEATER DURING INSTALLATION. FAILURE TO HEED

THIS WARNING MAY RESULT IN PROPERTY DAMAGE

OR PERSONAL INJURY.

Figure 5

"S"

"S"

AIR

FLO

W

AIR

FLO

W

NOTE:

WHEN TWO UNITS ARE JOINED SIDE BY SIDE IN

THE FIELD A SOLID PIECE OF SHEET METAL MUST

BE PROVIDED BY THE INSTALLER AT THE BACK OF

ADJACENT CENTER FLANGES, FRONT AND REAR.

D9193