Outdoor line voltage conduits leading into
the unit should be installed to prevent rain
from wetting any high voltage wire. Locate
the thermostat in accordance with the
instructions supplied with the thermostat.
All field wiring must have a minimum
temperature rating of 185°F (85°C). Control
wiring must be a minimum of 18 gauge wire
size. Control wiring must be sized for the
length of run.

Locate line voltage disconnect box per local
codes. If mounting the disconnect box to the
unit, never mount it to an unit access panel.
Possible locations include the front of the
blower or fi lter section, the outdoor air hood or
the rear of the supply plenum (See Figure 11).
Electrical conduit must be routed so as not to
interfere with removal of any access panel.

NOTICE: Should any original wire
supplied with the unit have to be
replaced, it must be replaced with wiring
having a temperature rating of at least
221°F (105°C).

Figure 9 - Standard Blower Cabinet, Single Duct Furnace with Supply Plenum & Various Options Shown

1. Mixed Air Controller

2. Return Firestat
3. Economizer
4. Filters
5. Blower Motor
6. Reverse Air Flow Switch
7. Clogged Filter Switch
8. High voltage Barrier and Lamp

and Circuit Breaker Mount

9. Main Connection Board

with Fan Time Delay and Func-
tion Relays

10. Power

Ventor

Relay

11. Freezestat
12. Supply

Firestat

13. Duct

Thermostat

14. Primary Safety Limit
15. Power

Ventor

Motor

16. Gas Piping Inlet
17. Gas

Valve

18. High Limit Safety Switch
19. Transformer
20. Electrical

Wiring

Inlet

21. High

Voltage

Terminal

Block

22. Door Safety Switch
23. Contactor
24. Centrifugal Blower Assembly
25. Damper

Motor

26. Outside and Return Dampers
27. Enthalpy

Controller

Economizer

28. Ambient

Lockout

Figure 10 - Electrical Cabinet

[Power Vent “PV” unit shown]