Figure 8 - Roof Curb Specifi cations

20-7/8"

(530)

20-7/8"

(530)

A

*

Return

Air

Opening

Supply

Air

Opening

E

*

Section

Y-Y

Section

X-X

Capacity

[ CA ]

Dimension

E *

10/15

20/25/50

30/35/60/70

40/80/12

26"

(660)

37"

(940)

48"

(1219)

53-1/2"

(1359)

Unit Type [ U T ] “RT, PV or AH”

* All Dimensions Shown Have Been Calculated To
Include A One (1) Inch Clearance Around Return
And Supply Ducts.

D3809-4

**

Rooftop

Arrangement

[ RA ]

C, E

J

L

C, E

J

L

J

Blower

High CFM

St'd.

Supply

Plenum

*

Dimension

A

Coil

50-7/8"

(1292)

87-1/16"

(2211)

113"

(2871)

76-7/8"

(1952)

139"

(3531)

113"

(2871)

139"

(3531)

Unit Specifications

( References )

Capacity

[ CA ]

10 - 40

20 - 40

10 - 40

50 - 80

50 - 80

50 - 80

12

**

Rooftop Arrangements [ RA ] B, D, G, K, M, P, S & U Are Without a

Return Air Dimensions For These Units Rooftop Openings. Refer To Unit Submittals For More Detail.

Unit Type [ U T ] “RT or PV”

**

[ RA ]

N, R

T

W

[ CA ]

*

A

24-7/8"

(631)

Unit Type [ UT ] “AH”

St'd.

Hi

Blower

Coil

Supply

61-1/16"

(1551)

87-1/16"

(2211)

20

or 40

20

or 40

20

or 40

TRI

SINGLE

DU

AL

FURNA

CE

D3809-1

2" (50)

3/8" (10) Clearance
Should Be Maintained
On Each Side To Insure
Proper Installation.

1-7/8" (22)

Anchor
Location

*

Field Supplied

By Others

D3809-2

4"

(102)

12"

(305)

Nailer
(Wood Strip)

Nail

*

Felt

*

Cant

*

1" (25)

Gasketing

Roof

Unit

Seal All Corners,
Seams & Gaps.

Unit Base

Side Rail Flange

With Curb Cap

Optional
Insulation

See Detail K

Detail K

Curb Rail
Ass'y.

Section Curb Side Rail

2-1/2"

(64)

Damper