XIV. GAS EQUIPMENT START-UP

Customer ____________________________________ Job Name & Number _________________________

PRE-INSPECTION INFORMATION

With power and gas off.

Type of Equip:

Unit Heater

Duct Furnace

Indoor

Rooftop

Serial Number

_________________________ Model Number __________________________

Name Plate Voltage:

_____________

Name Plate Amperage: _____________

Type of Gas:

Natural

LP

Tank Capacity ______ lbs.

Rating: ______ BTU @ ____ °F

______ kg

______ kw @ ____ °C

Are all panels, doors, vent caps in place?

Has the unit suffered any external damage?

Damage ______________________________

Does the gas piping and electric wiring appear to be installed in a professional manner?

Has the gas and electric been inspected by the local authority having jurisdiction?

Is the gas supply properly sized for the equipment?

Were the installation instructions followed when the equipment was installed?

Have all fi eld installed controls been installed?

Do you understand all the controls on this equipment? If not, contact your wholesaler or rep.

(DO NOT START this equipment unless you fully understand the controls.)

GENERAL

With power and gas off.

Make certain all packing has been removed.

Tighten all electrical terminals and connections.

Check damper linkages for tightness.

Check all fans & blowers for free movement.

Check all controls for proper settings.

Check all set screws on blowers and bearings.

Check belt tightness.

BLOWER

With power on and gas off.

Check voltage L1 _____ L2 _____ L3 _____

Check rotation of main blower.

Check motor amps L1 _____ L2 _____ L3 _____

Blower RPM _____________

Check air fi lters. (Record quantity & size.)

GAS HEATING

With power and gas on.

Inlet gas pressure.

____ in. W.C. or ____ kPa

Pilot & main burner ignition.

Manifold gas pressure. ____ in. W.C. or ____ kPa

Cycle on HIGH LIMIT.

Cycle fi restat and/or freezestat.

Check electronic modulation. Set at: __________

Cycle and check all other controls not listed.

Check operation of remote panel.

Entering air temp. _____ °F or ____ °C

Discharge air temp. (high fi re) ____ °F. or ____ °C

External static pressure ____ in. W.C. or ____ kPa

Cycle by thermostat or operating control.