Note: Please read sections 14 and 15 before proceeding.

14.

Installing the Steam Hose and the Fan module

NOTE: This unit is supplied with 2 feet of steam hose and therefore the distance between the fan module and
steam generator should be less than two feet, see fi gure 14a. Longer hoses at a length of 4 feet are available
from Thermolec. For distances up to 12 feet, a section of insulated copper pipe can be connected between
two pieces of steam hose.

14.1

The fan distribution module must have a minimum clearance of 2 feet from the ceiling or adjacent walls

and a minimum clearance of 3 feet in front of the faceplate. With these distances in mind measure a rectangle
of 9 1/8” wide by 6 1/4” high. The rectangle needs to be level with respect to the fl oor. Drill a small pilot hole
through each corner from the faceplate wall and through the other side of the wall. With a saw cut out the
rectangle from corner to corner. Take care not to drill through or cut any electrical wires or plumbing. Please
see fi gure 14b.

14.2

The opening at the back of the wall must be at least 1 3/4” wider on each side, 2” lower at the bottom

and fl ush with the top of the 4 pilot holes. Mark these points to make a larger rectangle and cut it out.

fan module

Acu Steam
steam generator

Fig. 14a

8 1/2”

front opening (faceplate side)

back opening

pilot hole drilled through entire wall

12 3/4”

9 1/8”

2”

min 1 3/4”

Fig. 14b

6 1/4”