Installing the EA401

Declassify the hazardous location before proceeding with any

installation or electrical wiring.

Caution: Installation or
electrical wiring in a
hazardous location
could result in serious
injury to personnel or
damage to property.

• Follow all appropriate electrical codes and use only approved electrical

fittings for the installation.

• Choose a wall location that is free of obstructions and permits space for ½”

NPT conduit runs

See: Figure 3 - Typical
Installation.

• Ensure mounting can support 16.5lbs. (7.5kg), plus the weight of any

peripheral equipment.

• Ensure that none of the electrical connection circuits are live.

• Use the template provided to locate and drill holes for mounting screws.

Use ¼” bolts or screws to mount the unit.

See: Figure 2 -
Dimensions.

• Secure the unit to the wall:

Tip: Use ¼” bolts or
screws to secure the unit
to the wall.

• Attach lower conduit nipples to the telephone and ensure a minimum five

thread engagement.

• Mount an approved explosion proof junction box within 45.7 cm (18") of the

telephone’s lower sealing cavity and bring telephone wires into this box.

Tip: Fittings compatible
with 1/2 inch NPT
nipples, conduit, or 1/2
inch explosion-proof
flexible couplings not
exceeding 45.7 mm (18
inches) may be fitted
directly.