installation diagrams - top inlet/outlet usage

Use of the top inlet water connection requires installation of an

inlet dip tube (refer to figure 19). The tube is supplied in the

heater. Follow caution labels if applying heat to this fitting. Do

not allow pipe dope to contact the plastic tube during installation.

tuBe inlet installation

figure 19

code restrictions

Use of the top inlet water connection is not permitted on

installations in the state of North Carolina, due to the material

of the tube (Polypropylene). Where such code restrictions exist,

use only lower inlet tank connection. This may also require a

heat trap - check local codes. The “Top Outlet” connection

may still be used on these applications. Plug or cap all unused

openings in the tank before filling with water.

temperature setting should not exceed

safe use temperature at fixtures. see water

temperature control and mixing ValVe warning

on page 12. if higher preheat temperatures are

necessary to oBtain adeQuate Booster output,

add an anti-scald ValVe for hot water supplied

to fixtures.