Locating the water heater, Clearances, Locating the water heater clearances – American Water Heater (A)BCG3 85T500-8N User Manual

Page 9: Caution, Installation considerations, Fire or explosion hazard

Advertising
background image

9

IS NOT SUBJeCT TO PhySICAL DAMAGe By A MOVING

VehICLe.
flammaBle items, PreSSUrIZeD CONTAINerS Or ANy

OTher POTeNTIAL FIre hAZArDOUS ArTICLeS MUST

NeVer Be PLACeD ON Or ADJACeNT TO The heATer.

OPeN CONTAINerS Or FLAMMABLe MATerIAL ShOULD

NOT Be STOreD Or USeD IN The SAMe rOOM WITh The

heATer.
The heATer MUST NOT Be LOCATeD IN AN AreA Where

IT WILL Be SUBJeCT TO FreeZING.
LOCATe IT NeAr A FLOOr DrAIN. The heATer ShOULD

Be LOCATeD IN AN AreA Where LeAkAGe FrOM The

heATer Or CONNeCTIONS WILL NOT reSULT IN DAMAGe

TO The ADJACeNT AreA Or TO LOWer FLOOrS OF The

STrUCTUre.
WheN SUCh LOCATIONS CANNOT Be AVOIDeD, A SUITABLe

DrAIN PAN ShOULD Be INSTALLeD UNDer The heATer.

Such pans should be fabricated with sides at least 2” deep, with

length and width at least 2” greater than the diameter of the heater

and must be piped to an adequate drain. The pan must not restrict

combustion air flow.

clearances

This water heater is approved for installation on combustible

flooring (with NSF Leg kit #9003425205) in an alcove when the

minimum clearance from any combustible construction is as

indicated in Figure 6 and Table 4.
In all installations the minimum combustible clearances from

vent piping shall be 6” (15.2 cm). Vent piping passing through a

combustible wall or ceiling must be a continuous run (no joints)

and retain the 6” (15.2 cm) clearance unless an approved reducing

thimble is used.
A service clearance of 24” (61 cm) should be maintained from

serviceable parts, such as relief valves, flue baffles, thermostats,

cleanout openings or drain valves.
The units are approved for installation with side, rear and ceiling

clearances as indicated below:

taBle 4

minimum clearances to comBustiBles in inches (mm)

model

"a"

right

side

"B"

left

side

"c"

Back

"d"

ceiling

(a)Bcg385t500-8n/

(a)Bcg385t500-8p

5"

(12.7 cm)

5"

(12.7 cm)

5"

(12.7 cm)

20"

(50.8 cm)

taBle 5

minimum clearances to noncomBustiBle construction

model

"a"

right

side

"B"

left

side

"c"

Back

"d"

ceiling

(a)Bcg385t500-8n/

(a)Bcg385t500-8p

0

0

0

12"

(30.5 cm)

locating the water heater

Property Damage Hazard

All water heaters eventually leak.

Do not install without adequate drainage.

CAUTION

When installing the heater, consideration must be given to

proper location. Location selected should be as close to the

stack or chimney as practicable, with adequate air supply and as

centralized with the piping system as possible.

Fire or Explosion Hazard

Read instruction manual before

installing, using or servicing

water heater.

Avoid all ignition sources if you smell gas.

Do not store or use gasoline or other flammable vapors and

liquids in the vicinity of this or any other appliance.

Use only the gas shown on the water heater rating label.

Keep ignition sources away from faucets after extended

periods of non-use.

Maintain required clearances to combustibles.

Do not expose water heater controls to excessive gas

pressure.

There IS A rISk IN USING FUeL BUrNING APPLIANCeS

SUCh AS GAS WATer heATerS IN rOOMS, GArAGeS Or

OTher AreAS Where GASOLINe, OTher FLAMMABLe

LIQUIDS Or eNGINe DrIVeN eQUIPMeNT Or VehICLeS Are

STOreD, OPerATeD Or rePAIreD. FLAMMABLe VAPOrS

Are heAVy AND TrAVeL ALONG The FLOOr AND MAy Be

IGNITeD By The heATer’S PILOT Or MAIN BUrNer FLAMeS

CAUSING FIre Or eXPLOSION. SOMe LOCAL CODeS

PerMIT OPerATION OF GAS APPLIANCeS IN SUCh AreAS

IF They Are INSTALLeD 18” Or MOre ABOVe The FLOOr.

ThIS MAy reDUCe The rISk IF LOCATION IN SUCh AN AreA

CANNOT Be AVOIDeD.
DO NOT INSTALL ThIS WATer heATer DIreCTLy ON A

CArPeTeD FLOOr. A FIre hAZArD MAy reSULT. Instead the

water heater must be placed on a metal or wood panel extending

beyond the full width and depth by at least 3 inches in any direction.

If the heater is installed in a carpeted alcove, the entire floor shall

be covered by the panel. Also, see the DrAINING requirements

in MAINTeNANCe Section.
The heATer ShALL Be LOCATeD Or PrOTeCTeD SO IT

installation considerations