Edwards Signaling 102 DeviceNet User Manual

Page 12

Advertising
background image

P/N 3100125 ISSUE 3

PAGE 12

4.

If using the optional Cat No. 102SIGMT-DN multi-tone module, connect the five position female connector on the
tone module to the upper set of male pins in the Triliptical DeviceNet Stackable Beacon Base. Set the selected tone
in accordance with the table below. Set the third Byte (Data Byte 2) in accordance with the table below in order to
access the required tone. "X" is the "Don't Care" State.

Switch Settings*

Tone

Bit3

Bit2

Bit1

Bit0

Tone Off

0

X

X

X

Stutter Beep

1

0

0

0

Continuous

1

0

0

1

3 Pulse Horn

1

0

1

0

Rapid Siren

1

0

1

1

Hi/Lo

1

1

0

0

Fast Whoop

1

1

0

1

Yeow

1

1

1

0

Beep

1

1

1

1

*1 is ON. 0 is OFF.

5.

Install the 102TBS-* front cover or the optional 102SIGMT-DN-G1 multi-tone module by tightening the two captive
front screws.

6.

Test the Triliptical DeviceNet Stackable Beacon to ensure that it operates as intended.

To test the device for functionality the unit must be connected to a DeviceNet network via the five (5) pin
connector. Turn on the network power supply and local power (if so configured) for the lamps. All lamps will
flash instantaneously (some lamps may not be visible) as the unit checks for proper lamp operation. The value of
the data byte in the master poll will be displayed on the lamps until it is changed by subsequent poll command.
The pre-defined poll connection has consume size of three (3) bytes, and a produce size of three (3) bytes. When
all the connections are released the lamps will display the last poll command data before release of the connection.

7.

The following is an Output Data Byte example

Byte 2

XXXX 1 001

Set

Tone

On

Set

Tone

Value 1

Byte 1

000 00001

Set

Lamp 1

to

Flashing

Set

Flash

Rate =

8OFPM

Byte 0

XXX 11111

Set

Five

Lamps

ON

8.

The following is an Input Data Byte example:

Byte 2

XXXX 1001

Sounder is

ON with

Tone

Value 1

Byte 1

XXX 00011

Lamp 2

was ON

before last poll

command

Byte 0

0XX 00001

Lamp 1 is

burned out

or missing

Local

Power

is OK

Advertising