Edwards Signaling 102 DeviceNet User Manual

Page 4

Advertising
background image

P/N 3100125 ISSUE 3

PAGE 4

For Units Configured with 4 Light Modules

BYTE

BIT7

BIT6

BIT5

BIT4

BIT3

BIT2

BIT1

BIT0

0

DON'T

DON'T

DON'T

DON'T

LMP 4

LMP 3

LMP 2

LMP 1

CARE

CARE

CARE

CARE

1 = ON

1 = ON

1 = ON

1 = ON

0 = OFF

0 = OFF

0 = OFF

0 = OFF

1

0

0

1

DON'T

LMP 4

LMP 3

LMP 2

LMP 1

45

CARE

1 = FLSH

1 = FLSH

1 = FLSH

1 = FLSH

FPM

0 = STDY

0 = STDY

0 = STDY

0 = STDY

1

0

1

0

DON'T

LMP 4

LMP 3

LMP 2

LMP 1

60

CARE

1 = FLSH

1 = FLSH

1 = FLSH

1 = FLSH

FPM

0 = STDY

0 = STDY

0 = STDY

0 = STDY

1

1

DON'T

DON'T

DON'T

LMP 4

LMP 3

LMP 2

LMP 1

80

CARE

CARE

CARE

1 = FLSH

1 = FLSH

1 = FLSH

1 = FLSH

FPM

0 = STDY

0 = STDY

0 = STDY

0 = STDY

1

0

0

0

DON'T

LMP 4

LMP 3

LMP 2

LMP 1

80 FPM

80 FPM

80 FPM

CARE

1 = FLSH

1 = FLSH

1 = FLSH

1 = FLSH

DEFLT

DEFLT

DEFLT

0 = STDY

0 = STDY

0 = STDY

0 = STDY

2

DON'T

DON'T

DON'T

DON'T

Sounder

Tone

Tone

Tone

CARE

CARE

CARE

CARE

1 = ON

MSB

LSB

0 = OFF

Output to the 102TBS-DN with the poll command from master node.

Data Byte 0 value indicates the lamps to be turned ON or OFF.

Data Byte 1 value indicates the ON lamps to be Steady ON or Flashing and the Flashing rate (45, 60 or 80 flashes
per minute) selected. Strobe units should always be set to Steady ON.

Data Byte 2 value indicates the sounder to be turned ON or OFF and the tone to be chosen.

For Units Configured with 5 Light Modules

BYTE

BIT7

BIT6

BIT5

BIT4

BIT3

BIT2

BIT1

BIT0

0

DON'T

DON'T

DON'T

LMP 5

LMP 4

LMP 3

LMP 2

LMP 1

CARE

CARE

CARE

1 = ON

1 = ON

1 = ON

1 = ON

1 = ON

0 = OFF

0 = OFF

0 = OFF

0 = OFF

0 = OFF

1

0

0

1

LMP 5

LMP 4

LMP 3

LMP 2

LMP 1

45

1 = FLSH

1 = FLSH

1 = FLSH

1 = FLSH

1 = FLSH

FPM

0 = STDY

0 = STDY

0 = STDY

0 = STDY

0 = STDY

1

0

1

0

LMP 5

LMP 4

LMP 3

LMP 2

LMP 1

60

1 = FLSH

1 = FLSH

1 = FLSH

1 = FLSH

1 = FLSH

FPM

0 = STDY

0 = STDY

0 = STDY

0 = STDY

0 = STDY

1

1

DON'T

DON'T

LMP 5

LMP 4

LMP 3

LMP 2

LMP 1

80

CARE

CARE

1 = FLSH

1 = FLSH

1 = FLSH

1 = FLSH

1 = FLSH

FPM

0 = STDY

0 = STDY

0 = STDY

0 = STDY

0 = STDY

1

0

0

0

LMP 5

LMP 4

LMP 3

LMP 2

LMP 1

80 FPM

80 FPM

80 FPM

1 = FLSH

1 = FLSH

1 = FLSH

1 = FLSH

1 = FLSH

DEFLT

DEFLT

DEFLT

0 = STDY

0 = STDY

0 = STDY

0 = STDY

0 = STDY

2

DON'T

DON'T

DON'T

DON'T

Sounder

Tone

Tone

Tone

CARE

CARE

CARE

CARE

1 = ON

MSB

LSB

0 = OFF

Advertising