Connection Object - Poll I/O Message Connection (Instance #2)

ATTR

ACCESS

DATA

ID

RULES

NAME

TYPE

VALUE

1

Get

State

USINT

State Dependent

2

Get

Instance type

USINT

0x01

3

Get

Xport class trigger

USINT

0x82

4

Get

Produced CONN. ID

UINT

0x3FF for MACID 63

5

Get

Consumed CONN. ID

UINT

0x5FD for MACID 63

6

Get

Initial COMM. Characteristics

UINT

0x01

7

Get/Set

Produced CONN. size

UINT

0x03

8

Get/Set

Consumed CONN. size

UINT

0x03

9

Get/Set

Expected packet rate

UINT

Application dependent

10

N/A

N/A

N/A

Not used

11

N/A

N/A

N/A

Not used

12

Get/Set

Watchdog timeout action

USINT

(0x00 Default) 0, 1, 2

13

Get

Produced path length

UINT

0x0006

14

Get

Produced path

ARRAY OF USINT

20.04.24.01.30.03

15

Get

Consumed path length

UINT

0x0006

16

Get

Consumed path

ARRAY of USINT

20.04.24.01.30.03

Connection Object Services:

SERVICE

SERVICE CODE

PARAMETERS

Get Attribute Single

0x0E

Attribute ID

Set Attribute Single

0x10

Attribute ID

ATTR

ACCESS

DATA

ID

RULES

NAME

TYPE

VALUE

1

Get

State

USINT

0x03

2

Get

Instance type

USINT

0x00

3

Get

Xport class trigger

USINT

0x83

4

Get

Produced CONN. ID

UINT

0x5FB for MACID 63

5

Get

Consumed CONN. ID

UINT

0x5FC for MACID 63

6

Get

Initial COMM. Characteristics

UINT

0x21

7

Get

Produced CONN. size

UINT

0x0007

8

Get

Consumed CONN. size

UINT

0x0007

9

Get/Set

Expected packet rate

UINT

Application dependent

10

N/A

N/A

N/A

Not used

11

N/A

N/A

N/A

Not used

12

Get/Set

Watchdog timeout action

USINT

0x01 Default

13

Get

Produced path length

UINT

0x0000

14

Get

Produced path

ARRAY OF USINT

<NULL>

15

Get

Consumed path length

UINT

0x0000

16

Get

Consumed path

ARRAY of USINT

<NULL>

2.5

Connection Object (Class ID = 5).

There are two instances of the Connection object in the 102TBS-DN. Instance #1 is assigned to the Explicit
Messaging Connection. Instance #2 is assigned to the Polled I/O Connection. The following table shows the
attributes and the pre-defined values where applicable. No class attributes are supported.

Connection Object - Explicit Message Connection (Instance #1)