2. Installation

Wiring the APS-6RF

12

APS-6RF Instruction PN 50893:B 7/20/00

Wiring the APS-6RF

This section contains instructions for wiring the Auxiliary Power Supply
as follows:

• Typical field wiring from an APS-6RF to a control panel.

• Wiring multiple APS-6RF power supplies.

• Connecting an APS-6RF to an IC module

Field Wiring an APS-6RF

You can use J1 and J2 in place of TB2 when the APS-6RF is powering
internal modules (such as an IC-4F, ICE-4F, TC-2F, TC-4F) with
compatible connectors.

Primary and Secondary Power Connections - See appendix for your
specific system information.

Caution: When finished wiring AC connections, install the press-fit
terminal block cover over TB1 AC connections.

Figure 4 Typical Wiring for an APS-6RF

!

J2

J9

J3

J1

TB2

JP3

JP2

Output Circuit 1: Power-limited
3 A @24 VDC (+10, –15%)

Primary Power
120 VAC or 240 VAC.

Output Circuit 1 (24 VDC)

Output Circuit 2 (24 VDC)

Secondary Power
24 VDC batteries.

Trouble Bus In/Out

Output Circuit 2: Power-limited
3 A @24 VDC (+10, –15%)

Earth Ground - Connects to
chassis or

EARTH

ground terminal on

main power supply. If two or more
units are connected, secondary
units connect to earth ground on the
previous APS-6RF in the chain.

A

P

S

-6R

si

de

brd.cd

r

BATT (+)

BATT (–)

HOT

NEUTRAL

EARTH

Output Circuit 3: Not Applicable

+

+

– + – + – +