Fire-Lite APS-6RF Auxiliary Power Supply User Manual
Page 8
1. Overview
Description
8
APS-6RF Instruction PN 50893:B 7/20/00
The figures below identify the features of the APS-6RF power supply:
Figure 2 APS-6RF Control Board
Figure 3 APS-6RF Main Board
J2
J9
J3
J1
TB
2
JP
3
JP
2
Fuse F1 for AC protection
(4A, 3AG, slow blow)
Three 24 VDC output circuits
Two (2) power-limited
One (1) non power-limited
Trouble In (J4) - Trouble Out (J3)
“P” style connectors for internal cabinet
connections
LED Status Indicators:
Green LED – Indicates AC power on
Yellow LED – Indicates loss of AC or battery
Fuse F2 for battery protection
(10A, 3AG, slow blow)
Jumpers JP2 and JP3 for
selecting 8-hour or 16-hour
delay for AC loss reporting
(default is immediate)
A
P
S
-6R
s
ide
b
rd.
c
d
r
JP
1
Jumper JP1 for selecting AC input voltage
(120 VAC default)
A
P
S
-6R
bo
a
rd.
c
d
r