The figures below identify the features of the APS-6RF power supply:

Figure 2 APS-6RF Control Board

Figure 3 APS-6RF Main Board

J2

J9

J3

J1

TB

2

JP

3

JP

2

Fuse F1 for AC protection
(4A, 3AG, slow blow)

Three 24 VDC output circuits
Two (2) power-limited
One (1) non power-limited

Trouble In (J4) - Trouble Out (J3)
“P” style connectors for internal cabinet
connections

LED Status Indicators:
Green LED – Indicates AC power on
Yellow LED – Indicates loss of AC or battery

Fuse F2 for battery protection
(10A, 3AG, slow blow)

Jumpers JP2 and JP3 for
selecting 8-hour or 16-hour
delay for AC loss reporting
(default is immediate)